Notes
Date Text
2017-05-25 07:25:27JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
  
 110.24 AVAILABLE FAULT CURRENT.
 (A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN
 DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD
 WITH THE
 MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKLNG(S)
 SHALL
 INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS
 PERFORMED
 AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
 ENVIRONMENT
 INVOLVED.
  
 (B) MODIFICATIONS. WHEN MODIFICATIONS TO THE ELECTRICAL
 INSTALLATION OCCUR THAT AFFECT THE MAXIMUM AVAILABLE
 FAULT
 CURRENT AT THE SERVICE, THE MAXIMUM AVAILABLE FAULT
 CURRENT
 SHALL BE VERIFIED OR RECALCULATED AS NECESSARY TO
 ENSURE THE
 SERVICE EQUIPMENT RATINGS ARE SUFTICIENT FOR THE
 MAXIMUM
 AVAILABLE FAULT CULTENT AT THE LINE TERMINALS OF THE
 EQUIPMENT.
 THE REQUIRED FIELD MARKING(S) IN LLO.24(A) SHALL BE
 ADJUSTED TO
 REFLECT THE NEW LEVEL OF MAXIMUM AVAILABLE FAULT
 CURRENT
  
 408.4 FIELD IDENTIFICATION REQUIRED.
 (B) SOURCE OF SUPPLY. ALL SWITCHBOARDS,SWITEHGEAR, AND
 PANELBOARDS SUPPLIED BY A FEEDER(S) IN OTHER THAN ONE-
 OR
 TWO-FAMILY DWELLINGS SHALL BE MARKED TO INDICATE EACH
 DEVICE
 OR EQUIPMENT WHERE THE POWER ORIGINATES.
  
 C405.5 INTERIOR LIGHTING POWER REQUIREMENTS
 (PRESCRIPTIVE).
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING
 POWER CALCULATED UNDER SECTION C405.5.1 IS NO GREATER
 THAN THE
 INTERIOR LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.2.
  
 C405.5.1 TOTAL CONNECTED INTERIOR LIGHTING POWER.
 THE TOTAL CONNECTED INTERIOR LIGHTING POWER (WATTS)
 SHALL BE THE
 SUM OF THE WATTS OF ALL INTERIOR LIGHTING EQUIPMENT AS
 DETERMINED
 IN ACCORDANCE WITH SECTIONS C405.5.1.1 THROUGH
 C405.5.1.4.
  
 C405.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 SPECIFIED
 IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND C405.2.4.
  
 C405.2.1 MANUAL LIGHTING CONTROLS.
 ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS
 THAT MEET
 THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND C405.2.1.2.
  
  
  
  