Plan Review Notes
Plan Review Notes For Permit 17050621
Permit Number 17050621
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-22 15:46:01 
 05/25/17 CALLED MICHAEL POLK. TOLD HIM THAT THE ENERGY
 CALCULATIONS NEED TO BE REVISED AND RE-SUBMITTED.
 ENERGY CALCULATIONS ARE REQUIRED FOR NEW A/C WORK ON
 EXISTING SIDE OF HOUSE. JG.
  
 RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISE THE EQUIPMENT SIZING CALCULATIONS:
 CALCULATIONS NEED TO BE DONE FOR THE ACTUAL ORIENTATION
 OF THE BUILDING. THIS HOUSE IS FACING SOUTH-WEST.
 REVISE CALCULATIONS USING THE CORRECT ORIENTATION AS
 REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 2- ENGINEER OF RECORD TO SPECIFY ON THE A/C PLAN THE
 EQUIPMENT MANUFACTURER AND MODEL NUMBER SPECIFIED ON
 THE EQUIPMENT SIZING CALCULATIONS. SEC. 107.3.5.3(10)
 CITY AMENDMENTS.
  
 3- ENGINEER OF RECORD TO SPECIFY THE CFM'S ON THE A/C
 PLAN. SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 4- ENGINEER OF RECORD TO SHOW ON THE A/C PLAN
 COMPLIANCE WITH THE BALANCED RETURN AIR AS REQUIRED BY
 SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 5- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE 2 COPIES AS REQUIRED BY SEC. 107.1 CITY
 AMENDMENTS. ONLY ONE COPY WAS SUBMITTED.
  
 B) INFORMATION ON TOP OF FORM IS INCORRECT: REVISE THE
 NAME OF PROJECT, NAME OF BUILDER, NAME OF CONTRACTOR,
 PERMIT OFFICE (CITY OF WEST PALM BEACH NOT PALM BEACH),
 JURISDICTION NUMBER (704600 NOT 601000) AND CLIMATE
 ZONE (1A NOT 2).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) IT IS NOT CLEAR IF THE ENERGY CALCULATIONS SUBMITTED
 ARE FOR THE ENTIRE HOUSE OR JUST ONE PART OF THE HOUSE.
 THE SQUARE FOOTAGE ON ITEM #6 (1122S.F.) IS FOR AN
 ADDITION THAT WAS DONE IN 2002. PLEASE COORDINATE
 ENERGY CALCULATIONS WITH EQUIPMENT SIZING CALCULATIONS.
 SEE SQUARE FOOTAGE CONSIDERED ON THE EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 D) NUMBER OF BEDROOMS IS INCORRECT. COORDINATE WITH
 ITEM #5(C) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E) PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 MANUFACTURER'S SPECIFICATIONS FOR ALL THE EXISTING
 WINDOWS AND DOORS SHOWING COMPLIANCE WITH THE U-FACTOR
 AND SHGC SPECIFIED ON ITEM #7. THIS IS ONLY REQUIRED
 WHEN A FACTOR OTHER THAN THE PROGRAM DEFAULT FACTOR IS
 USED FOR THE ENERGY CALCULATIONS. SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
  
 F) REVISE FLOOR SQUARE FOOTAGE ON ITEM #8. COORDINATE
 WITH ITEM #5(C) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 G) ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. PERSON PREPARING THE ENERGY CALCULATIONS TO
 PROVIDE SKETCHES AND COMPLETE INFORMATION FOR THE
 CEILING FANS SHOWING COMPLIANCE WITH SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 H) ENERGY CALCULATIONS NEED THE NAME OF THE PERSON
 PREPARING THE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION.
  
 I) PROVIDE THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION.
  
 J) OWNER OR LEGALLY AUTHORIZED AGENT TO CERTIFY AT THE
 BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION.
  
 K) COORDINATE SPACES INFORMATION ON PAGE 2 OF 4 WITH
 ITEM #5(C). THE KITCHEN IS IN THE OLD SECTION OF THE
 HOUSE NOT IN THE 2002 ADDITION. CLARIFY/REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 L) THE ROOF TYPE AND ROOF MATERIALS SHOWN ON PAGE 2 OF
 5 IS INCORRECT. SEE PLANS AND REVISE AS REQUIRED. THERE
 ARE TWO DIFFERENT TYPES OF ROOF AND MATERIALS. REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 M) REVISE THE BUILDING ORIENTATION OF THE WALL AND
 WINDOWS INFORMATION SHOWN ON PAGE OF 4 TO MATCH THE
 ACTUAL BUILDING ORIENTATION. NOTE: HOUSE IS FACING
 SOUTH-WEST
  
 N) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]