Text |
2017-05-22 15:46:01 | |
| 05/25/17 CALLED MICHAEL POLK. TOLD HIM THAT THE ENERGY |
| CALCULATIONS NEED TO BE REVISED AND RE-SUBMITTED. |
| ENERGY CALCULATIONS ARE REQUIRED FOR NEW A/C WORK ON |
| EXISTING SIDE OF HOUSE. JG. |
| |
| RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- REVISE THE EQUIPMENT SIZING CALCULATIONS: |
| CALCULATIONS NEED TO BE DONE FOR THE ACTUAL ORIENTATION |
| OF THE BUILDING. THIS HOUSE IS FACING SOUTH-WEST. |
| REVISE CALCULATIONS USING THE CORRECT ORIENTATION AS |
| REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH |
| EDITION (2014). |
| |
| 2- ENGINEER OF RECORD TO SPECIFY ON THE A/C PLAN THE |
| EQUIPMENT MANUFACTURER AND MODEL NUMBER SPECIFIED ON |
| THE EQUIPMENT SIZING CALCULATIONS. SEC. 107.3.5.3(10) |
| CITY AMENDMENTS. |
| |
| 3- ENGINEER OF RECORD TO SPECIFY THE CFM'S ON THE A/C |
| PLAN. SEC. 107.3.5.3(10) CITY AMENDMENTS. |
| |
| 4- ENGINEER OF RECORD TO SHOW ON THE A/C PLAN |
| COMPLIANCE WITH THE BALANCED RETURN AIR AS REQUIRED BY |
| SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 5- REVISE ENERGY CALCULATIONS SUBMITTED: |
| A) PROVIDE 2 COPIES AS REQUIRED BY SEC. 107.1 CITY |
| AMENDMENTS. ONLY ONE COPY WAS SUBMITTED. |
| |
| B) INFORMATION ON TOP OF FORM IS INCORRECT: REVISE THE |
| NAME OF PROJECT, NAME OF BUILDER, NAME OF CONTRACTOR, |
| PERMIT OFFICE (CITY OF WEST PALM BEACH NOT PALM BEACH), |
| JURISDICTION NUMBER (704600 NOT 601000) AND CLIMATE |
| ZONE (1A NOT 2). |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| C) IT IS NOT CLEAR IF THE ENERGY CALCULATIONS SUBMITTED |
| ARE FOR THE ENTIRE HOUSE OR JUST ONE PART OF THE HOUSE. |
| THE SQUARE FOOTAGE ON ITEM #6 (1122S.F.) IS FOR AN |
| ADDITION THAT WAS DONE IN 2002. PLEASE COORDINATE |
| ENERGY CALCULATIONS WITH EQUIPMENT SIZING CALCULATIONS. |
| SEE SQUARE FOOTAGE CONSIDERED ON THE EQUIPMENT SIZING |
| CALCULATIONS. REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| D) NUMBER OF BEDROOMS IS INCORRECT. COORDINATE WITH |
| ITEM #5(C) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| E) PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE |
| MANUFACTURER'S SPECIFICATIONS FOR ALL THE EXISTING |
| WINDOWS AND DOORS SHOWING COMPLIANCE WITH THE U-FACTOR |
| AND SHGC SPECIFIED ON ITEM #7. THIS IS ONLY REQUIRED |
| WHEN A FACTOR OTHER THAN THE PROGRAM DEFAULT FACTOR IS |
| USED FOR THE ENERGY CALCULATIONS. SEC. R405.4.3 |
| FBC-ENERGY CONSERVATION. |
| |
| F) REVISE FLOOR SQUARE FOOTAGE ON ITEM #8. COORDINATE |
| WITH ITEM #5(C) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| G) ENERGY CALCULATIONS ARE TAKING THE CEILING FAN |
| CREDIT. PERSON PREPARING THE ENERGY CALCULATIONS TO |
| PROVIDE SKETCHES AND COMPLETE INFORMATION FOR THE |
| CEILING FANS SHOWING COMPLIANCE WITH SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| H) ENERGY CALCULATIONS NEED THE NAME OF THE PERSON |
| PREPARING THE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| R405.4.2 FBC-ENERGY CONSERVATION. |
| |
| I) PROVIDE THE INSPECTION CHECKLIST AS REQUIRED BY SEC. |
| R405.4.2 FBC-ENERGY CONSERVATION. |
| |
| J) OWNER OR LEGALLY AUTHORIZED AGENT TO CERTIFY AT THE |
| BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| K) COORDINATE SPACES INFORMATION ON PAGE 2 OF 4 WITH |
| ITEM #5(C). THE KITCHEN IS IN THE OLD SECTION OF THE |
| HOUSE NOT IN THE 2002 ADDITION. CLARIFY/REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| L) THE ROOF TYPE AND ROOF MATERIALS SHOWN ON PAGE 2 OF |
| 5 IS INCORRECT. SEE PLANS AND REVISE AS REQUIRED. THERE |
| ARE TWO DIFFERENT TYPES OF ROOF AND MATERIALS. REVISE |
| AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| M) REVISE THE BUILDING ORIENTATION OF THE WALL AND |
| WINDOWS INFORMATION SHOWN ON PAGE OF 4 TO MATCH THE |
| ACTUAL BUILDING ORIENTATION. NOTE: HOUSE IS FACING |
| SOUTH-WEST |
| |
| N) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY |
| CONSERVATION. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |