2017-05-17 10:49:09 | PERMIT# 17050583: FIRE SPRINKLER PLAN REVIEW IS |
| APPROVED WITH THE FOLLOWING FIRE CODE COMMENTS. NOTE: |
| THIS PLAN WAS EXPEDITED PER REQUEST FROM CHAKIERA |
| MORGAN 772-283-2320. GROUP ONE SAFETY. |
| |
| APPROVAL SHALL NOT RELIEVE THE APPLICANT OF THE |
| RESPONSIBILITY OF COMPLIANCE WITH THE FIRE CODE. |
| |
| NFPA 1.14.2, 2012 EDITION THE APPLICANT SHALL BE |
| RESPONSIBLE TO ENSURE THAT THE FOLLOWING CONDITIONS ARE |
| MET: (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF |
| CONSTRUCTION |
| DOCUMENTS ON SITE. INCLUDING FIRE SPRINKLER HEAD |
| SPECIFICATION SHEET. |
| |
| NFPA 13-6.2.6 SPECIAL COATINGS. 6.2.6.1 CORROSION |
| RESISTANT.6.2.6.1.1 LISTED CORROSION-RESISTANT |
| SPRINKLERS SHALL BE INSTALLED IN LOCATIONS WHERE |
| CHEMICALS, MOISTURE, OR OTHER CORROSIVE VAPORS |
| SUFFICIENT TO CAUSE CORROSION OF SUCH DEVICES EXIST. |
| 6.2.6.1.2* UNLESS THE REQUIREMENTS OF 6.2.6.1.3 ARE |
| MET, CORROSION-RESISTANT COATINGS SHALL BE APPLIED ONLY |
| BY THE MANUFACTURER OF THE SPRINKLER AND IN ACCORDANCE |
| WITH THE REQUIREMENTS OF 6.2.6.1.3. |
| |
| NFPA 13-6.2.8 GUARDS. SPRINKLERS SUBJECT TO MECHANICAL |
| INJURY SHALL BE PROTECTED WITH LISTED GUARDS. |
| |
| NFPA 13-8.15.12.3, 2010 EDITION: SPRINKLER ACCESS. |
| ACCESS SHALL BE PROVIDED TO ALL SPRINKLERS FOR |
| INSPECTION, TESTING, AND MAINTENANCE. |
| |
| NFPA 14-6.3.7.1: SYSTEM WATER SUPPLY VALVES, ISOLATION |
| CONTROL VALVES, AND OTHER VALVES IN FEED MAINS SHALL BE |
| SUPERVISED IN AN APPROVED MANNER IN THE OPEN POSITION |
| BY ONE OF THE FOLLOWING METHODS: |
| (1) A CENTRAL STATION, PROPRIETARY, OR REMOTE STATION |
| SIGNALING SERVICE.(2) A LOCAL SIGNALING SERVICE THAT |
| INITIATES AN AUDIBLE SIGNAL AT A CONSTANTLY ATTENDED |
| LOCATION.(3) LOCKING OF VALVES IN THE OPEN POSITION. |
| (4) SEALING OF VALVES AND AN APPROVED WEEKLY RECORDED |
| INSPECTION WHERE VALVES ARE LOCATED WITHIN FENCED |
| ENCLOSURES UNDER THE CONTROL OF THE OWNER. 6.3.7.2 |
| UNDERGROUND GATE VALVES WITH ROADWAY BOXES SHALL NOT BE |
| REQUIRED TO BE SUPERVISED. |
| |
| FRANK STALLWORTH, FIRE INSPECTOR I |
| WEST PALM BEACH FIRE PREVENTION BUREAU |