Plan Review Notes For Permit 17050546 |
Permit Number |
17050546 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-09-21 13:23:00 | 2ND REVIEW FBC-2014 MECHANICAL | | SUBMITTAL #17050546 | | BRIGHTLINE MASTER #16070715 | | 9/21/18 | | | | COMMENTS #4 & 5 FROM THE 1ST REVIEW STILL EXIST | | | | 4) PLEASE REVISE THE FAN SCHEDULE ON THE PLAN TO MATCH | | THE SUBMITTALS. (PLEASE SEE SHEET M1301- MASTER PERMT | | #16070715). | | | | 5) MOTORIZED DAMPERS: THE SUBMITTAL FOR THE DUROZONE | | MOTORIZED DAMPER DOES NOT INDICATE THE UNIT IS CLASS 1A | | RATED AND, DOES NOT EXCEED THE MAXIMUM LEAKAGE RATE | | WHEN TESTED IN ACCORDANCE WITH AMCA 500D- SEE SECTION | | C402.4.5.2 FBC-14 ENERGY CONSERVATION. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|