2017-05-24 10:39:371ST REVIEW FBC-2014 MECHANICAL
 SUBMITTAL #17050546
 BRIGHTLINE MASTER #16070715
 5/24/17
  
 1) EF-25-1: THE SUBMITTAL FOR THE PENNBARRY D10 SMOKE
 EXHAUST FAN DOES NOT PROVIDE EVIDENCE THAT THE FAN IS
 RATED AND CERTIFIED BY THE MANUFACTURER FOR THE
 PROBABLE TEMPERATURE RISE AS REQUIRED BY SECTION
 513.10.1 FBC-14 MECHANICAL. THE SUBMITTAL DOES NOT
 INDICATE THE FAN IS UL 705 LISTED AND LABELED PER THE
 ENGINEER'S NOTES IN THE FAN SCHEDULE (SHEET M1301), AND
 DOES NOT INDICATE THE FAN WILL BE EQUIPPED WITH TWO
 BELTS. PLEASE REVIEW THE SUBMITTAL FOR COMPLIANCE.
  
 2) DUCTS: REFER TO SECTION 513.10.2 FBC-14 MECHANICAL
 AND INDICATE WHICH DUCTS IN THE SUBMITTAL PACKAGE ARE
 DESIGNATED FOR SMOKE CONTROL AND EXHAUST, AND PROVIDE
 EVIDENCE THAT THE DESIGNATED DUCTS HAVE BEEN TESTED FOR
 RESISTANCE TO TEMPERATURE RISE AND PRESSURE, AND LEAK
 TESTED TO 1.5 TIMES THE MAXIMUM DESIGN PRESSURE.
  
 3) IT DOES NOT APPEAR THAT THE PENNBARRY SMOKE CONTROL
 FAN SUBMITTALS INDICATE THAT THE SELECTED SMOKE CONTROL
 FANS ARE EQUIPPED WITH TWO BELTS AS REQUIRED BY SECTION
 513.10.5 FBC-14 MECHANICAL, AND ALSO BY THE ENGINEER OF
 RECORD'S DESIGN- SEE SUBMITTAL REVIEW COMMENTS BY C.
 BUI.
  
 4) PLEASE REVISE THE FAN SCHEDULE ON THE PLAN TO MATCH
 THE SUBMITTALS.
  
 5) MOTORIZED DAMPERS: THE SUBMITTAL FOR THE DUROZONE
 MOTORIZED DAMPER DOES NOT INDICATE THE UNIT IS CLASS 1A
 RATED AND, DOES NOT EXCEED THE MAXIMUM LEAKAGE RATE
 WHEN TESTED IN ACCORDANCE WITH AMCA 500D- SEE SECTION
 C402.4.5.2 FBC-14 ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  