2017-06-06 12:36:09 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17050545 | | 6/6/17 | | | | RESULTS: DENIED. | | | | 1) HVAC NOTE #11 INDICATES THE PLAN IS INTENDED TO BE | | AN "AS-BUILT OF CONTRACTOR DESIGN", HOWEVER NO DUCTWORK | | LATYOUT AND DETAILS HAVE BEEN PROVIDED. | | | | 2) PROVIDE BATH EXHAUST DUCT DETAILS- TYPE AND SIZE OF | | DUCTS AND SUBDUCT CONNECTIONS TO EXISTING CHASES. | | | | 3) THE ARCHITECT OF RECORD SHALL PROVIDE HIS SIGNATURE | | AND SEAL ON BOTH SETS OF PLANS SUBMITTED IN ACCORDANCE | | WITH SECTION 61G1-16.003 FLORIDA ADMINISTRATIVE CODE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|