Plan Review Notes
Plan Review Notes For Permit 17050545
Permit Number 17050545
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-18 14:49:081ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050545
 5/18/17
  
 RESULTS: DENIED.
  
 1) EXHAUST VENTILATION FOR THE KITCHEN IS REQUIRED PER
 TABLE 403.3. PROVIDE A SYSTEM THAT PROVIDES EITHER 25
 CFMS CONTINUOUSLY, OR 100 CFMS INTERMITTENTLY.
  
 2) PROVIDE PRODUCT SPEC SHEETS FOR THE NEW RANGE AND
 RANGE HOOD AND INCLUDE EQUIPMENT SCHEDULES ON THE PLAN-
 SECTION 505.
  
 3) SHOW THE EXHAUST DUCT RUN AND TERMINATION LOCATION.
 PLEASE INCLUDE THE TYPE AND SIZE OF DUCT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved