2017-05-16 06:34:48 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. FBC B 603, DETAIL A-A1.0 SPECS WOOD AS ALTERNATE, |
| ISN'T THIS A HIGH RISE? REVISE DETAIL OR CLARIFY. |
| |
| 2. DEMOLITION NOTES, REMOVE NOTES NOT APPLICABLE TO |
| THIS PROJECT (BURIED TANKS, SOIL TESTING, ETC.). |
| |
| 3. PROVIDE TEST REPORTS FOR UNDERLAYMENT; THREE |
| REQUIRED SHOWING COMPLIANCE WITH: |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| |
| 4. FLOOR PLANS 1 AND 2, PAGE A1.0 APPEAR TO PROPOSE A 4 |
| INCH CHANGE IN ELEVATION TO THE AREA SOUTH OF THE |
| KITCHEN. IF THIS IS INTENDED FOR THE COUNTERTOP, |
| RE-LOCATE THE DIMENSION AND REVISE ELEVATIONS C AND E. |
| |
| IF THIS IS FOR THE FLOOR - THE PURPOSE OF THIS IS NOT |
| CLEAR, NO CORRESPONDING DETAIL PROVIDED, ROOM |
| DESIGNATION FOR THE AREA NOT PROVIDED. FBC B CHAPTER |
| 10, FBC 107, REVISE TO CLARIFY. |
| |
| |