Plan Review Notes
Plan Review Notes For Permit 17050520
Permit Number 17050520
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-19 14:11:371ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050520
 5/19/17
  
 RESULTS: DENIED
  
 1) THE PLAN SHOWS NEW TRANSFER OPENINGS FROM THE TENANT
 SPACES INTO THE CORRIDOR. CLARIFY IF AIR IS TO BE
 TRANSFERRED INTO THE CORRIDOR, OR ABOVE THE CORRIDOR
 CEILING IN A PLENUM SPACE. SEE SECTIONS 601.2 AND
 601.2.1 FOR EXCEPTIONS AND ALLOWANCES.
  
 2) PROVIDE THE FLEX DUCT SIZES ON THE DUCT LAYOUT PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719