Plan Review Notes
Plan Review Notes For Permit 17050520
Permit Number 17050520
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-05 14:13:22CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SHEET E0.1, ELECTRICAL SPECIFICATIONS, # C.11
 REFERENCES THE CITY OF BOYNTON BEACH CODES. PLEASE
 REMOVE NOTE FOR THIS PLAN. FBC 107.2.1
 2. SHEET E0.1, SHEET INDEX STATES THERE IS AN
 ELECTRICAL RISER DIAGRAM SHEET # E5.1. THIS SHEET IS
 MISSING. CLARIFY AND/OR CORRECT. FBC 107.2.1
 3. SPECIFY METHOD OF ATTACHING AND/OR SUPPORTING THE
 LAY IN LIGHT FIXTURES. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  