Plan Review Notes For Permit 17050520 |
Permit Number |
17050520 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-06-05 14:13:22 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW COMMENTS: | | | | 1. SHEET E0.1, ELECTRICAL SPECIFICATIONS, # C.11 | | REFERENCES THE CITY OF BOYNTON BEACH CODES. PLEASE | | REMOVE NOTE FOR THIS PLAN. FBC 107.2.1 | | 2. SHEET E0.1, SHEET INDEX STATES THERE IS AN | | ELECTRICAL RISER DIAGRAM SHEET # E5.1. THIS SHEET IS | | MISSING. CLARIFY AND/OR CORRECT. FBC 107.2.1 | | 3. SPECIFY METHOD OF ATTACHING AND/OR SUPPORTING THE | | LAY IN LIGHT FIXTURES. FBC 107.2.1 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|