2017-05-26 16:56:542014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050520
 ADD: 250 S. AUSTRALIAN AVE. SUITE: 1300
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 26, 2017
 ACTION: DENIED
  
 1) SHEET ALS1.1 THE RIGHT SIDE OF THE SHEET SHOWS A
 COMMON PATH OF TRAVEL OF 70.5 FEET. THE COMMON PATH OF
 TRAVEL STOPS SHORT, PLEASE CONTINUE THE COMMON PATH OF
 TRAVEL PAST THE ELEVATOR BANK TO WHERE YOU HAVE A
 CHOICE BETWEEN WHICH EXIT YOU WOULD WANT TO TRAVEL TOO.
 ELEVATORS WILL BE CALLED BACK TO THE 1ST FLOOR FOR THE
 FIREMANS USE. COMMON PATH OF TRAVEL IS LIMITED TO 100
 FT. PLEASE PROVIDE THE OVERALL DISTANCE. 2014 FBC-B
 TABLE 1014.3.
  
 2) SHEET A1.1.1 SHOWS THE MAIL ROOM DOOR 1318 MISSING
 THE REQUIRED 18 INCHES ON THE LATCH SIDE.
 ACCESS CODE 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1.
  
 3) SHEET A2.0:
 3A) THE WINDOW SCHEDULE DOES NOT SHOW COMPLIANCE WITH
 SAFETY GLAZING REQUIREMENTS PER TABLE 2406.2(2) OF THE
 2014 FBC-B.
  
 3B) THE DOOR TYPES SHOW A DOOR TYPE A WITH A SINGLE
 LIGHT WITHIN THE FRAME OF THE DOOR. THE PLANS DO NOT
 ADDRESS THE NEED FOR SAFETY GLAZING FOR THE GLAZING IN
 THE DOOR ITSELF. SHOW COMPLIANCE WITH TABLE 2406.2(2)
 OF THE 2014 FBC-B.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER