Plan Review Notes For Permit 17050505 |
Permit Number |
17050505 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-22 13:07:19 | APPROVED WITH EXCEPTIONS | | G2427.8 (503.8) VENTING SYSTEM TERMINATION LOCATION. | | THE LOCATION OF VENTING SYSTEM TERMINATIONS SHALL | | COMPLY WITH THE FOLLOWING (SEE APPENDIX C): | | 1. A MECHANICAL DRAFT VENTING SYSTEM SHALL TERMINATE AT | | LEAST 3 FEET (914 MM) ABOVE ANY FORCED-AIR INLET | | LOCATED WITHIN 10 FEET (3048 MM). | | 2. A MECHANICAL DRAFT VENTING SYSTEM, EXCLUDING | | DIRECT-VENT APPLIANCES, SHALL TERMINATE AT LEAST 4 FEET | | (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR | | 1 FOOT (305 MM) ABOVE ANY DOOR, OPERABLE WINDOW, OR | | GRAVITY AIR INLET INTO ANY BUILDING. THE BOTTOM OF THE | | VENT TERMINAL SHALL BE LOCATED AT LEAST 12 INCHES (305 | | MM) ABOVE FINISHED GROUND LEVEL. |
|