Plan Review Notes
Plan Review Notes For Permit 17050505
Permit Number 17050505
Review Stop P
Sequence Number 1
Notes
Date Text
2017-05-22 13:07:19APPROVED WITH EXCEPTIONS
 G2427.8 (503.8) VENTING SYSTEM TERMINATION LOCATION.
 THE LOCATION OF VENTING SYSTEM TERMINATIONS SHALL
 COMPLY WITH THE FOLLOWING (SEE APPENDIX C):
 1. A MECHANICAL DRAFT VENTING SYSTEM SHALL TERMINATE AT
 LEAST 3 FEET (914 MM) ABOVE ANY FORCED-AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 2. A MECHANICAL DRAFT VENTING SYSTEM, EXCLUDING
 DIRECT-VENT APPLIANCES, SHALL TERMINATE AT LEAST 4 FEET
 (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR
 1 FOOT (305 MM) ABOVE ANY DOOR, OPERABLE WINDOW, OR
 GRAVITY AIR INLET INTO ANY BUILDING. THE BOTTOM OF THE
 VENT TERMINAL SHALL BE LOCATED AT LEAST 12 INCHES (305
 MM) ABOVE FINISHED GROUND LEVEL.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved