Plan Review Notes
Plan Review Notes For Permit 17050462
Permit Number 17050462
Review Stop B
Sequence Number 1
Notes
Date Text
2017-05-11 08:26:512014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050462
 ADD: 428 29TH ST.
 CONT: CHASE ROOFING
 TEL: 954-680-8588
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 1ST REVIEW
 DATE: THURS. MAY 11/2017
 ACTION: DENIED
 1) THE IMPROVEMENT VALUE OF THE STRUCTURE IS LISTED BY
 PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE AT
 $453,992.00 DOLLARS. PLEASE SHOW YOU ARE GOING TO MEET
 CODE COMPLIANCE WITH SECTION 708.8.1 OF THE 2014
 EXISTING BUILDING CODE.
 708.8.1 ROOF-TO-WALL CONNECTIONS FOR SITE-BUILT SINGLE
 FAMILY RESIDENTIAL STRUCTURES. WHERE REQUIRED BY
 SECTION 708.8, THE INTERSECTION OF ROOF FRAMING WITH
 THE WALL BELOW SHALL PROVIDE SUFFICIENT RESISTANCE TO
 MEET THE UPLIFT LOADS SPECIFIED IN TABLE 708.8.1,
 EITHER BECAUSE OF EXISTING CONDITIONS OR THROUGH
 RETROFIT MEASURES. AS AN ALTERNATIVE TO AN ENGINEERED
 DESIGN, THE PRESCRIPTIVE RETROFIT SOLUTIONS PROVIDED IN
 SECTIONS 708.8.1.1 THROUGH 708.8.1.7 SHALL BE ACCEPTED
 AS MEETING THE MANDATED ROOF-TO-WALL RETROFIT
 REQUIREMENTS.
 2) THE CONTRACTOR HAS SUBMITTED A MIAMI-DADE NOA GAF
 TPO NOA: 15-0203/24
 PAGE 15 OF 17
 MEMBRANE TYPE: TPO
 DECK TYPE: 1I
 SYSTEM E(2)
 MAXIMUM DESIGN PRESSURE: -67.5
  
 WHEN VIEWING THIS ADDRESS WITH GOOGLE AND PICTOMETRY
 THIS STRUCTURE IS 2 STORIES AND A PARAPET LESS THAN 3
 FEET IN HEIGHT. THIS MEANS THERE IS ROOF ZONES, 1
 INTERIOR, ZONE: 2 PARAMETER AND ZONE 3: CORNER ZONES.
 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715