2017-05-15 08:54:041ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17050398
 5/15/17
  
 RESULTS: DENIED.
  
 1) THE AC PLAN IS CONFUSING BECAUSE IT APPEARS TO SHOW
 AN AIR HANDLER POSITIONED INLINE IN THE MIDDLE OF A
 SUPPLY DUCT RUN FROM ANOTHER AIR HANDLER. BOTH OF THESE
 AIR HANDLERS ARE LABELED AHU 49D14AA, AND EACH HAS A
 RETURN DUCT CONNECTION FROM THE DISPLAY ROOM: PLEASE
 CLARIFY HOW THESE SYSTEMS ARE FUNCTIONING TOGETHER.
  
 2) THE PLAN IS LACKING SOME BASIC NOTES AND DETAILS
 THAT WOULD HELP EXPEDITE THE REVIEW:
  
 A) IDENTIFY ALL ROOMS AND SPACES.
  
 B) INDICATE WHICH DUCTS AND AIR DEVICES ARE EXISTING
 (E) OR NEW (N).
  
 C) INDICATE ALL SUPPLY AND RETURN DUCT SIZES.
  
 3) PROVIDE RETURN AIR FROM THE NEW OFFICES 1 & 2-
 SECTION 601.5.
  
 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE THAT NO O/A
 DUCT IS SHOWN ON THE PLAN.
  
 5) INDICATE HOW THE STORAGE AND EQUIPMENT ROOMS ARE
 BEING VENTILATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER