Plan Review Notes
Plan Review Notes For Permit 17050398
Permit Number 17050398
Review Stop E
Sequence Number 1
Notes
Date Text
2017-05-23 17:31:28CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 THE FOLLOWING INFORMATION NEEDS TO PLACE ON THE PLANS
 FOR REVIEW.
 PAGE 2
  
 110.24 AVAILABLE FAULT CURRENT.
 (A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN
 DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD
 WITH THE
 MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKLNG(S)
 SHALL
 INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS
 PERFORMED
 AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
 ENVIRONMENT
 INVOLVED.
  
 (B) MODIFICATIONS. WHEN MODIFICATIONS TO THE ELECTRICAL
 INSTALLATION OCCUR THAT AFFECT THE MAXIMUM AVAILABLE
 FAULT
 CURRENT AT THE SERVICE, THE MAXIMUM AVAILABLE FAULT
 CURRENT
 SHALL BE VERIFIED OR RECALCULATED AS NECESSARY TO
 ENSURE THE
 SERVICE EQUIPMENT RATINGS ARE SUFTICIENT FOR THE
 MAXIMUM
 AVAILABLE FAULT CULTENT AT THE LINE TERMINALS OF THE
 EQUIPMENT.
 THE REQUIRED FIELD MARKING(S) IN LLO.24(A) SHALL BE
 ADJUSTED TO
 REFLECT THE NEW LEVEL OF MAXIMUM AVAILABLE FAULT
 CURRENT
  
 C405.5 INTERIOR LIGHTING POWER REQUIREMENTS
 (PRESCRIPTIVE).
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.1 IS NO GREATER THAN
 THE INTERIOR LIGHTING
 POWER CALCULATED UNDER SECTION C405.5.2.
  
 C405.5.1 TOTAL CONNECTED INTERIOR LIGHTING POWER.
 THE TOTAL CONNECTED INTERIOR LIGHTING POWER (WATTS)
 SHALL BE THE SUM OF THE
 WATTS OF ALL INTERIOR LIGHTING EQUIPMENT AS DETERMINED
 IN ACCORDANCE WITH
 SECTIONS C405.5.1.1 THROUGH C405.5.1.4
  
 C405.2.1.1 INTERIOR LIGHTING CONTROLS.
 EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING
 PARTITIONS SHALL HAVE AT
 LEAST ONE MANUAL CONTROL FOR THE LIGHTING SERVING THAT
 AREA. THE REQUIRED
 CONTROLS SHALL BE LOCATED WITHIN THE AREA SERVED BY THE
 CONTROLS OR BE A
 REMOTE SWITCH THAT IDENTIFIES THE LIGHTS SERVED AND
 INDICATES THEIR STATUS.
  
 408.4 FIELD IDENTIFICATION REQUIRED.
 (A) CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS
 TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE
 IDENTIFICATION
 SHALL INCLUDE AN APPROVED DEGREE OF DETAIL THAT
 ALLOWS EACH CIRCUIT TO BE DISTINGUISHED FROM ALL
 OTHERS.
 SPARE POSITIONS THAT CONTAIN UNUSED OVERCUN'ENT DEVICES
 OR
 SWITCHES SHALL BE DESCRIBED ACCORDINGLY. THE
 IDENTIFICATION
 SHALL BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS
 LOCATED ON THE
 FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANELBOARD
 AND AT EACH SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD
 OR
 SWITCHGEAR. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER
 THAT
 DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY.
  
 (B) SOURCE OF SUPPLY. ALL SWITCHBOARDS,SWITEHGEAR, AND
 PANELBOARDS SUPPLIED BY A FEEDER(S) IN OTHER THAN ONE-
 OR
 TWO-FAMILY DWELLINGS SHALL BE MARKED TO INDICATE EACH
 DEVICE
 OR EQUIPMENT WHERE THE POWER ORIGINATES.
  
  
  
  
  
  
  
  
  
  
 .
  