2017-05-23 17:31:28 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| |
| THE FOLLOWING INFORMATION NEEDS TO PLACE ON THE PLANS |
| FOR REVIEW. |
| PAGE 2 |
| |
| 110.24 AVAILABLE FAULT CURRENT. |
| (A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN |
| DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD |
| WITH THE |
| MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKLNG(S) |
| SHALL |
| INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS |
| PERFORMED |
| AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE |
| ENVIRONMENT |
| INVOLVED. |
| |
| (B) MODIFICATIONS. WHEN MODIFICATIONS TO THE ELECTRICAL |
| INSTALLATION OCCUR THAT AFFECT THE MAXIMUM AVAILABLE |
| FAULT |
| CURRENT AT THE SERVICE, THE MAXIMUM AVAILABLE FAULT |
| CURRENT |
| SHALL BE VERIFIED OR RECALCULATED AS NECESSARY TO |
| ENSURE THE |
| SERVICE EQUIPMENT RATINGS ARE SUFTICIENT FOR THE |
| MAXIMUM |
| AVAILABLE FAULT CULTENT AT THE LINE TERMINALS OF THE |
| EQUIPMENT. |
| THE REQUIRED FIELD MARKING(S) IN LLO.24(A) SHALL BE |
| ADJUSTED TO |
| REFLECT THE NEW LEVEL OF MAXIMUM AVAILABLE FAULT |
| CURRENT |
| |
| C405.5 INTERIOR LIGHTING POWER REQUIREMENTS |
| (PRESCRIPTIVE). |
| A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL |
| CONNECTED LIGHTING POWER |
| CALCULATED UNDER SECTION C405.5.1 IS NO GREATER THAN |
| THE INTERIOR LIGHTING |
| POWER CALCULATED UNDER SECTION C405.5.2. |
| |
| C405.5.1 TOTAL CONNECTED INTERIOR LIGHTING POWER. |
| THE TOTAL CONNECTED INTERIOR LIGHTING POWER (WATTS) |
| SHALL BE THE SUM OF THE |
| WATTS OF ALL INTERIOR LIGHTING EQUIPMENT AS DETERMINED |
| IN ACCORDANCE WITH |
| SECTIONS C405.5.1.1 THROUGH C405.5.1.4 |
| |
| C405.2.1.1 INTERIOR LIGHTING CONTROLS. |
| EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING |
| PARTITIONS SHALL HAVE AT |
| LEAST ONE MANUAL CONTROL FOR THE LIGHTING SERVING THAT |
| AREA. THE REQUIRED |
| CONTROLS SHALL BE LOCATED WITHIN THE AREA SERVED BY THE |
| CONTROLS OR BE A |
| REMOTE SWITCH THAT IDENTIFIES THE LIGHTS SERVED AND |
| INDICATES THEIR STATUS. |
| |
| 408.4 FIELD IDENTIFICATION REQUIRED. |
| (A) CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY |
| CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| IDENTIFIED AS |
| TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE |
| IDENTIFICATION |
| SHALL INCLUDE AN APPROVED DEGREE OF DETAIL THAT |
| ALLOWS EACH CIRCUIT TO BE DISTINGUISHED FROM ALL |
| OTHERS. |
| SPARE POSITIONS THAT CONTAIN UNUSED OVERCUN'ENT DEVICES |
| OR |
| SWITCHES SHALL BE DESCRIBED ACCORDINGLY. THE |
| IDENTIFICATION |
| SHALL BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS |
| LOCATED ON THE |
| FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A |
| PANELBOARD |
| AND AT EACH SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD |
| OR |
| SWITCHGEAR. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER |
| THAT |
| DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY. |
| |
| (B) SOURCE OF SUPPLY. ALL SWITCHBOARDS,SWITEHGEAR, AND |
| PANELBOARDS SUPPLIED BY A FEEDER(S) IN OTHER THAN ONE- |
| OR |
| TWO-FAMILY DWELLINGS SHALL BE MARKED TO INDICATE EACH |
| DEVICE |
| OR EQUIPMENT WHERE THE POWER ORIGINATES. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| . |
| |