2017-05-16 08:25:00 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17050398 |
| ADD: 6620 S. DIXIE HWY. |
| CONT: FLAGLER BUILDING SYSTEMS |
| TEL: 561-596-3983 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. MAY 16/ 2017 |
| ACTION: DENIED |
| |
| 1) SHEET 1 UNDER THE HEADING DESIGN STANDARDS DO NOT |
| PROVIDE THE MINIMUM REQUIREMENTS FOR PLAN REVIEW: |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 1. LIST THE EXISTING THE 2014 FBC- BUILDING CODE |
| 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503) |
| 4. IS THIS FIRE SPRINKLERED OR NOT? |
| 5.. IS THIS A CHANGE OF OCCUPANCY? |
| |
| 2) THE DESIGNER OF RECORD HAS NOT INDICATED WHICH |
| DESIGN METHOD THE PLANS WERE DESIGNED TOO? |
| 2014 FBC-EXIST. BUILD. SECTION 301 COMPLIANCE METHODS. |
| 301.1 GENERAL. THE REPAIR, ALTERATION, CHANGE OF |
| OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING |
| BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS LISTED |
| IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE |
| APPLICANT. IF THE |
| |
| 3) SHEET 1 LIST THE WIND DESIGN AS 170 VULT MPH BUT THE |
| PRESSURES ONLY STATE +/- 50. THESE PRESSURES ARE TOO |
| LOW FOR VULT AND TOO HIGH FOR VASD? 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 4) SHEET 1 INDICATES A LARGE DISPLAY AREA IN THE CENTER |
| OF THE TENANT SPACE IS THIS A MERCANTILE OR BUSINESS |
| OCCUPANCY, OCCUPANCY IS NOT PROVIDED. THERE IS A EXIT |
| LIGHT DIRECTING EGRESS THROUGH THE STORAGE ROOM. THE |
| BACK OF THE TENANT SPACE INDICATES INDICATES REAL |
| ESTATE RECORDS (STORAGE). 2014 FBC-B 1014.2. |
| |
| 5) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| |
| 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| 7) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, |
| ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING |
| SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| THE TESTS. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| ON SUBSEQUENT REVIEWS. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |