2018-03-06 17:10:01 | RESIDENTIAL (R3) ADDITION, SECOND MECHANICAL REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- THERE ARE NO CITY RECORDS SHOWING ANY A/C WORK IN |
| THIS HOUSE. PROVIDE COMPLETE A/C PLANS SHOWING ALL THE |
| EQUIPMENT AND DUCTWORK. SPECIFY THE EQUIPMENT |
| MANUFACTURER AND MODEL. COORDINATE INFORMATION WITH |
| EQUIPMENT SIZING CALCULATIONS. SEE ITEM #2 BELOW. |
| SEC. 107.3.5.3(10) CITY AMENDMENTS. |
| |
| RESPONSE: MECHANICAL PLAN DRAWING M-1 SUBMITTED ONLY |
| PROVIDES INFORMATION FOR THE ADDITION. THERE ARE NO |
| PERMITS FOR THE A/C UNIT. PROVIDE ALL THE INFORMATION |
| REQUESTED ABOVE. |
| |
| 2- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY |
| SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| RESPONSE: CALCULATIONS SUBMITTED ARE ONLY FOR THE |
| ADDITION. NEED TO PROVIDE COMPLETE EQUIPMENT SIZING |
| CALCULATIONS FOR ENTIRE HOUSE SINCE THERE ARE NO |
| PERMITS FOR THE A/C EQUIPMENT. PROVIDE COMPLETE |
| INFORMATION FOR THE EQUIPMENT AS REQUIRED BY SEC. |
| R403.6 FBC-ENERGY CONSERVATION. NOTE: COORDINATE |
| INFORMATION WITH THE ENERGY CALCULATIONS. IT LOOKS LIKE |
| THE WINDOW INFORMATION DOESN'T MATCH INFORMATION SHOWN |
| ON THE ENERGY CALCULATIONS. |
| |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON"T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |