Plan Review Notes
Plan Review Notes For Permit 17050393
Permit Number 17050393
Review Stop M
Sequence Number 2
Notes
Date Text
2018-03-06 17:10:01RESIDENTIAL (R3) ADDITION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- THERE ARE NO CITY RECORDS SHOWING ANY A/C WORK IN
 THIS HOUSE. PROVIDE COMPLETE A/C PLANS SHOWING ALL THE
 EQUIPMENT AND DUCTWORK. SPECIFY THE EQUIPMENT
 MANUFACTURER AND MODEL. COORDINATE INFORMATION WITH
 EQUIPMENT SIZING CALCULATIONS. SEE ITEM #2 BELOW.
 SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 RESPONSE: MECHANICAL PLAN DRAWING M-1 SUBMITTED ONLY
 PROVIDES INFORMATION FOR THE ADDITION. THERE ARE NO
 PERMITS FOR THE A/C UNIT. PROVIDE ALL THE INFORMATION
 REQUESTED ABOVE.
  
 2- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 RESPONSE: CALCULATIONS SUBMITTED ARE ONLY FOR THE
 ADDITION. NEED TO PROVIDE COMPLETE EQUIPMENT SIZING
 CALCULATIONS FOR ENTIRE HOUSE SINCE THERE ARE NO
 PERMITS FOR THE A/C EQUIPMENT. PROVIDE COMPLETE
 INFORMATION FOR THE EQUIPMENT AS REQUIRED BY SEC.
 R403.6 FBC-ENERGY CONSERVATION. NOTE: COORDINATE
 INFORMATION WITH THE ENERGY CALCULATIONS. IT LOOKS LIKE
 THE WINDOW INFORMATION DOESN'T MATCH INFORMATION SHOWN
 ON THE ENERGY CALCULATIONS.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON"T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  