Date |
Text |
2018-03-05 16:51:57 | ADDITION, SECOND BUILDING REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| NOTE: THIS CAN BE DONE LATER WHEN THE PLANS ARE |
| APPROVED AND PERMIT CARD IS READY TO BE PROCESSED. |
| |
| 2- ENERGY CALCULATIONS SUBMITTED: |
| A) OWNER TO SIGN THE ENERGY CALCULATIONS AS REQUIRED BY |
| SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2017). |
| |
| B) DUCT WORK INSULATION R-VALUE IN ITEM #11(A) NEEDS TO |
| BE REVISED. ACCORDING TO TABLE R402A NEED R-8 |
| INSULATION FOR DUCTWORK LOCATED IN THE ATTIC. SEC. |
| R101.5.1.1.1 FBC-ENERGY CONSERVATION. |
| |
| C) ITEM # 11(B) INDICATES THAT THE AHU LOCATION IS THE |
| GARAGE. THERE IS NOT GARAGE IN THIS HOUSE. SEE PLANS |
| AND REVISE AS REQUIRED. SEC. R101.5.1.1.1 FBC-ENERGY |
| CONSERVATION. NOTE: COORDINATE WITH A/C PLANS. SEE |
| MECHANICAL COMMENTS. |
| |
| D) NEED TO COMPLETE THE TABLE R402B AS REQUIRED BY |
| GENERAL INSTRUCTIONS NOTE #3 ON THE FRONT PAGE OF FORM |
| R402-2014 SUBMITTED. COMPLETE TABLE R402B AS REQUIRED. |
| SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION. |
| |
| E) COMPLETE INFORMATION ON TOP OF FORM. NEED THE |
| OWNER'S NAME AND BUILDER'S NAME. SEC. R101.5.1.1.1 |
| FBC-ENERGY CONSERVATION. |
| |
| 3- VALUATION WAS UPDATED TO $12,544 AS REQUIRED BY SEC. |
| 109.3 CITY AMENDMENTS. THE PERMIT FEE BALANCE DUE IS |
| $130.91. |
| |
| 4-WALL SECTION ON SHEET 02: |
| SPECIFIED LOCATION OF ROOF VENTS DON'T PROVIDE CROSS |
| VENTILATION AS REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL. |
| VENTS LOCATED AT 6'-0" O.C. DON'T PROVIDE VENTILATION |
| TO THE 2X12 ROOF JOISTS THAT ARE BETWEEN VENTS. |
| REMEMBER THAT ROOF FRAMING MEMBERS ARE 2X12 SOLID |
| JOISTS NOT ENGINEERED TRUSSES. THERE IS NOT CROSS |
| VENTILATION. REVISE AS REQUIRED. |
| |
| 5- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) FLAT ROOF. ONLY THE COVER PAGE OF NOA 17-0824.11 WAS |
| SUBMITTED. PROVIDE COMPLETE PRODUCT APPROVAL AND, |
| CLEARLY MARK WHICH APPROVED ASSEMBLY FROM THE PRODUCT |
| APPROVAL SUBMITTED IS GOING TO BE INSTALLED TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES. IF THE SELECTED |
| ASSEMBLY DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF |
| ZONES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL |
| BE REQUIRED. |
| |
| B) SINGLE HUNG WINDOWS: ONLY THE COVER PAGE OF NOA |
| 15-0602.06 WAS SUBMITTED. PROVIDE COMPLETE PRODUCT |
| APPROVAL. |
| |
| C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| NOTE: PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND |
| ONLY THE PAGE SHOWING THE SPECIFIED CONNECTOR OR DESIGN |
| PROFESSIONAL TO LIST THE FLORIDA PRODUCT APPROVAL |
| NUMBER NEXT TO EACH SPECIFIED CONNECTOR. |
| |
| D) PRECAST LINTELS SPECIFIED ON PLANS. REPEAT COMMENT. |
| NOT ADDRESSED AT ALL. |
| |
| 6- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON"T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |