Plan Review Notes For Permit 17050393 |
Permit Number |
17050393 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-06-06 18:00:28 | 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | FAC 61G20-3.001 FOR: | | A) FLAT ROOF SYSTEM TO BE INSTALLED. NOTE: SPECIFY | | WHICH APPROVED ASSEMBLY FROM THE PRODUCT APPROVAL | | SUBMITTED IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE | | WITH THE DESIGN PRESSURES. IF THE SELECTED ASSEMBLY | | DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, | | THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL BE | | REQUIRED. | | |
|