Plan Review Notes
Plan Review Notes For Permit 17050393
Permit Number 17050393
Review Stop M
Sequence Number 1
Notes
Date Text
2017-06-06 17:50:15RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- SCOPE OF WORK ON SHEET 01 SPECIFIES "ADD REAR A/C
 ADDITION W/BATH". THERE IS NO INFORMATION SUBMITTED
 SHOWING HOW THE PROPOSED ADDITION IS GOING TO HAVE
 CONDITIONED AIR. NOTE: THERE ARE NO CITY RECORDS
 SHOWING ANY A/C WORK IN THIS HOUSE. PROVIDE COMPLETE
 A/C PLANS SHOWING ALL THE EQUIPMENT AND DUCTWORK.
 SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL.
 SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 2- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON"T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  