Plan Review Notes For Permit 17050393 |
Permit Number |
17050393 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-06-06 17:50:15 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- SCOPE OF WORK ON SHEET 01 SPECIFIES "ADD REAR A/C | | ADDITION W/BATH". THERE IS NO INFORMATION SUBMITTED | | SHOWING HOW THE PROPOSED ADDITION IS GOING TO HAVE | | CONDITIONED AIR. NOTE: THERE ARE NO CITY RECORDS | | SHOWING ANY A/C WORK IN THIS HOUSE. PROVIDE COMPLETE | | A/C PLANS SHOWING ALL THE EQUIPMENT AND DUCTWORK. | | SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL. | | SEC. 107.3.5.3(10) CITY AMENDMENTS. | | | | 2- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY | | SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | (2014). | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | DRAWING. DON"T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | FOR REFERENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|