Plan Review Notes
Plan Review Notes For Permit 17050350
Permit Number 17050350
Review Stop B
Sequence Number 1
Notes
Date Text
2017-05-16 10:22:472014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050350
 ADD: 600 NORTHPOINT PKWAY/ REPLACEMENT OF ROOF TOP A/C
 UNIT
 CONT: FLORIDA MECHANICAL LLC
 TEL: 561-261-4651
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 16, 2017
 ACTION: DENIED
  
 1) IT WOULD APPEAR THAT JOSEPH F. MINICUZZI P. E. IS
 THE ENGINEER FOR THE PROJECT AND MAHMOUD MAAMOURI THE
 DELEGATE ENGINEER. THE ENGINEER FOR THE PROJECT WILL
 NEED TO REVIEW THE DELEGATE ENGINEERS SUBMITTAL AND
 REVIEW AND APPROVE WITH A SHOP DRAWING STAMP OF
 APPROVAL.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 2) COMPLIED.
  
 3) THIS IS EITHER A CASE OF THE WIND DESIGN DOCUMENTS
 NEED TO BE SIGNED AND SEALED ( BY AN ENGINEER)
 FL ADMIN CODE 61G15-23.002 ENGINEERS OR THE DESIGNER OF
 RECORD TO REVIEW THE COMPUTER GENERATED CALCULATIONS (
 BY THE DELEGATE ENGINEER) AS PART OF THE REVIEW PROCESS
 AND IF IN AGREEMENT APPLY HIS SHOP DRAWING STAMP OF
 APPROVAL. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEERING.
  
 4) THERE IS BOTH A UNKNOWN AND DISCREPANCY BETWEEN THE
 S-1 SHEET AND CURB PRODUCT DATA SUBMITTAL. THE S1 SHEET
 UNDER THE HEADING MECHANICAL UNIT ROOF TOP ATTACHMENT
 INDICATES (14) #12 SMS PER BRACKET EQUALLY SPACED, HOW
 MANY BRACKETS, TOTAL. WHEREAS IN THE CURB PRODUCT DATA
 DOCUMENTS SHEET S4 DATED 3/29/17 INDICATES THE BRACKET
 TO THE UNIT AND CURB W/ #12 OR ? INCH SELF ?DRILLING
 SCREWS. THE CLIP ONLY SHOWS A TOTAL OF 6 HOLES OR ONLY
 3 FASTENERS PER SIDE WHERE THE S1 SHEET WOULD HAVE 7
 FASTENERS PER SIDE.
 DISCREPANCY IN PLANS? 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  