2017-05-16 10:22:47 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17050350 |
| ADD: 600 NORTHPOINT PKWAY/ REPLACEMENT OF ROOF TOP A/C |
| UNIT |
| CONT: FLORIDA MECHANICAL LLC |
| TEL: 561-261-4651 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. MAY 16, 2017 |
| ACTION: DENIED |
| |
| 1) IT WOULD APPEAR THAT JOSEPH F. MINICUZZI P. E. IS |
| THE ENGINEER FOR THE PROJECT AND MAHMOUD MAAMOURI THE |
| DELEGATE ENGINEER. THE ENGINEER FOR THE PROJECT WILL |
| NEED TO REVIEW THE DELEGATE ENGINEERS SUBMITTAL AND |
| REVIEW AND APPROVE WITH A SHOP DRAWING STAMP OF |
| APPROVAL. |
| 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| RECORD FOR REVIEW. |
| |
| 2) COMPLIED. |
| |
| 3) THIS IS EITHER A CASE OF THE WIND DESIGN DOCUMENTS |
| NEED TO BE SIGNED AND SEALED ( BY AN ENGINEER) |
| FL ADMIN CODE 61G15-23.002 ENGINEERS OR THE DESIGNER OF |
| RECORD TO REVIEW THE COMPUTER GENERATED CALCULATIONS ( |
| BY THE DELEGATE ENGINEER) AS PART OF THE REVIEW PROCESS |
| AND IF IN AGREEMENT APPLY HIS SHOP DRAWING STAMP OF |
| APPROVAL. FL 61G-15-30.006 (3) THE DELEGATED |
| ENGINEERING. |
| |
| 4) THERE IS BOTH A UNKNOWN AND DISCREPANCY BETWEEN THE |
| S-1 SHEET AND CURB PRODUCT DATA SUBMITTAL. THE S1 SHEET |
| UNDER THE HEADING MECHANICAL UNIT ROOF TOP ATTACHMENT |
| INDICATES (14) #12 SMS PER BRACKET EQUALLY SPACED, HOW |
| MANY BRACKETS, TOTAL. WHEREAS IN THE CURB PRODUCT DATA |
| DOCUMENTS SHEET S4 DATED 3/29/17 INDICATES THE BRACKET |
| TO THE UNIT AND CURB W/ #12 OR ? INCH SELF ?DRILLING |
| SCREWS. THE CLIP ONLY SHOWS A TOTAL OF 6 HOLES OR ONLY |
| 3 FASTENERS PER SIDE WHERE THE S1 SHEET WOULD HAVE 7 |
| FASTENERS PER SIDE. |
| DISCREPANCY IN PLANS? 107.2.1.3 ADDITIONAL INFORMATION |
| IS REQUIRED. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |