Plan Review Notes
Plan Review Notes For Permit 17050336
Permit Number 17050336
Review Stop M
Sequence Number 1
Notes
Date Text
2017-06-07 10:11:19PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW THAT THE CONVERTED SPACE IS IN COMPLIANCE WITH
 FBC-R303.9 REQUIRED HEATING. WHEN THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60 DEGREES F ,
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A MINIMUM ROOM
 TEMPERATURE OF 68 DEGREES F AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
  
 2) THERE IS AN AIRHANDLER SHOWN IN THE NEW CLOSET ON
 THE PROPOSED FLOOR PLAN. FBC - 107.3.5.3 PROVIDE TWO
 SETS OF A MECHANICAL PLAN TO SHOW EQUIPMENT AND
 LOCATION AND DUCT SYSTEMS PER FBC-R M16 & BATH EXHAUST
 PER FBC-R M15.
  
 3) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS FOR THE NEW
 EQUIPMENT.
  
 4) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR
 R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE
 FORMS AS REQUIRED.
  
 5)