2017-05-31 08:30:59CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 1. SMOKE ALARMS NOT PERMITTED WITHIN 3 FEET OF A
 CEILING FAN. PROVIDE CORRECTION. NFPA 72 11.8.3.5
 2. PROVIDE FLOOR PLAN SHOWING LOCATIONS OF EXISTING
 SMOKE ALARMS IN RESIDENCE. IF NONE ARE EXISTING, OR NOT
 TO CODE, SHOW AS NEW INSTALLATION WITH INTERCONNECTION.
 FBC R314.5, R314.3.1
 3. SHOW AFCI PROTECTION REQUIRED PER NEC 210.12 AND FBC
 RESIDENTIAL. FBC R E3902.12
 4. PROVIDE ELECTRICAL PERMIT APPLICATION WITH SCOPE AND
 VALUE OF WORK AND LISTED. FBC 105.1, FBC 109.3
  