Date |
Text |
2017-06-07 09:30:45 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR |
| R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE |
| FORMS AS REQUIRED. THE FORMS ARE REQUIRED TO HAVE THE |
| NAME OF THE PREPARER AND THE SIGNATURE OF THE |
| OWNER/AGENT. |
| |
| 2) SUBMIT ELEVATIONS OF THE STRUCTURE THAT SPECIFY |
| CEILING HEIGHT, ROOF HEIGHT & SLOPE, FINISH FLOOR |
| HEIGHT ABOVE GRADE, ETC. FBC-R305, R301.2.1, FBC107.2.1 |
| |
| 3) PROVIDE WALL SECTIONS THAT SHOW WALL TYPE, INTERIOR |
| AND EXTERIOR FINISHES, INSULATION, ETC. FBC 107.2.1 & |
| FBC ENERGY CONSERVATION R103.2 |
| |
| 4) PROVIDE FLOOR PLANS WITH ALL DIMENSIONS SPECIFIED. |
| FBC-R304.4 AND FBC 107.2.1 |
| |
| 5) PROVIDE AREA TABULATIONS THAT SPECIFIES THE EXISTING |
| HABITABLE SPACE AND NON-HABITABLE SPACES FOR THE |
| STRUCTURE AND THE SPACE THAT IS BEING CONVERTED TO |
| HABITABLE SPACE. THE PALM BEACH COUNTY PROPERTY |
| APPRAISER AND THE CITY OF WEST PALM BEACH RECORDS |
| INDICATE THAT THIS ENTIRE AREA IS A GARAGE WITH A TWO |
| FIXTURE BATHROOM. THE PLANS INDICATE THAT THERE IS AN |
| EXISTING POOL CABANA IN A PORTION OF THE GARAGE. THERE |
| ARE NO RECORDS OF THE CABANA AT THE CITY. FBC 107.2.1 |
| |
| 6) PROVIDE A FLOOR PLAN THAT SHOWS THE ENTIRE STRUCTURE |
| AND LABEL THE ROOMS OF THE EXISTING HOUSE ARE ADJACENT |
| TO THE GARAGE ON THE FLOOR PLANS. FBC 107.2.1 |
| |
| 7) SHOW THE LOCATION OF THE ATTIC ACCESS FBC-R807.1 |
| BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION |
| SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT |
| EXCEED 30 SQUARE FEET (2.8 M2) AND HAVE A VERTICAL |
| HEIGHT OF 30 INCHES (762 MM) OR GREATER. THE VERTICAL |
| HEIGHT SHALL BE MEASURED FROM THE TOP OF THE CEILING |
| FRAMING MEMBERS TO THE UNDERSIDE OF THE ROOF FRAMING |
| MEMBERS. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS |
| THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND |
| SHALL BE LOCATED IN A HALLWAY OR OTHER READILY |
| ACCESSIBLE LOCATION. WHEN LOCATED IN A WALL, THE |
| OPENING SHALL BE A MINIMUM OF 22 INCHES WIDE BY 30 |
| INCHES HIGH. WHEN THE ACCESS IS LOCATED IN A CEILING, |
| MINIMUM UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL |
| BE AT SOME POINT 30 INCHES (762 MM) ABOVE THE ACCESS |
| MEASURED VERTICALLY FROM THE BOTTOM OF CEILING FRAMING |
| MEMBERS. SEE SECTION M1305.1.3 FOR ACCESS REQUIREMENTS |
| WHERE MECHANICAL EQUIPMENT IS LOCATED IN ATTICS. |
| |
| 8) THE WINDOW THAT IS SPECIFIED ON THE PLANS DOES NOT |
| COMPLY WITH FBC-R310.1 EMERGENCY ESCAPE AND RESCUE |
| REQUIRED. BASEMENTS, HABITABLE ATTICS AND EVERY |
| SLEEPING ROOM SHALL HAVE AT LEAST ONE OPERABLE |
| EMERGENCY ESCAPE AND RESCUE OPENING. WHERE EMERGENCY |
| ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY SHALL HAVE |
| A SILL HEIGHT OF NOT MORE THAN 44 INCHES (1118 MM) |
| ABOVE THE FLOOR. FBC-R310.1.1 ALL EMERGENCY ESCAPE AND |
| RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING |
| OF 5.7 SQUARE FEET (0.530 M2). EXCEPTION: GRADE FLOOR |
| OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5 |
| SQUARE FEET (0.465 M2). FBC-R310.1.2 THE MINIMUM NET |
| CLEAR OPENING HEIGHT SHALL BE 24 INCHES (610 MM). |
| FBC-R310.1.3 THE MINIMUM NET CLEAR OPENING WIDTH SHALL |
| BE 20 INCHES (508 MM). |
| |
| 9) SHOW THAT THE GARAGE CONVERSION COMPLIES WITH |
| FBC-R404.1.6 HEIGHT ABOVE FINISHED GRADE. CONCRETE AND |
| MASONRY FOUNDATION WALLS SHALL EXTEND ABOVE THE |
| FINISHED GRADE ADJACENT TO THE FOUNDATION AT ALL POINTS |
| A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY VENEER IS |
| USED AND A MINIMUM OF 6 INCHES (152 MM) ELSEWHERE. |
| |
| 10) THE VASD WINDSPEED ON S1 IS INCORRECT. THE VASD IS |
| 132 MPH FOR THIS PROJECT. FBC-R301.2.1.3 |
| |
| 11) THE STRUCTURAL PLANS S1 ARE REQUIRED TO HAVE THE |
| FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN |
| SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT |
| ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE |
| ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS |
| AND DOCUMENTS. |
| |
| 12) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THE EXTERIOR DOOR AND WINDOWS IN THE GARAGE THAT |
| HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. |
| |
| 13) SHOW COMPLIANCE WITH FBC-R303.9 FOR REQUIRED |
| HEATING. SEE MECHANICAL REVIEW COMMENTS. |
| |
| 14) PLANS WILL BE REQUIRED TO HAVE AN IMPACT FEE REVIEW |
| BY PALM BEACH COUNTY. SEE THE IMPACT REVIEW COMMENTS. |
| |
| 15) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |