2017-06-12 12:06:23 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE BOTTOM OF THE MIRROR ABOVE THE LAVATORY SHALL BE |
| 40" ABOVE FINISHED FLOOR. PER FBC ACC 603.3 MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 2. THE SIDE WALL GRAB BAR DOES NOT COMPLY WITH. FBC ACC |
| 604.5.1 SIDE WALL. |
| THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) |
| LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM |
| THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM |
| FROM THE REAR WALL. |
| |
| 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 602.4 SPOUT |
| HEIGHT. |
| SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE |
| THE FINISH FLOOR OR GROUND. |
| |
| 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. |
| SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 |
| INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| |
| 602.2 CLEAR FLOOR SPACE. |
| UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED. |
| |
| 4. ALL FLOOR DRAIN SHALL HAVE TRAP PRIMERS PLEASE SHOW |
| COMPLIANCE WITH. FBC PL1002.4 TRAP SEALS. |
| EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS |
| THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 |
| MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO |
| ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO |
| LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE |
| INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE |
| TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A |
| TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR |
| ASSE 1044. |
| |
| 5. LAVATORY'S IN BATHROOM ARE REQUIRED TO HAVE TEMPERED |
| WATER ONLY. PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC |
| HAND-WASHING FACILITIES. |
| TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |