Notes |
Date |
Text |
2017-05-09 10:36:45 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1) THE UNDERGROUNG FRIE LINE SHALL BE INSTALLED PER THE | | REQUIREMENTS OF NFPA 24, STANDARD FOR THE INSTALLATION | | OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES, | | 2010 EDITION. | | | | | | 2) PLEASE PROVIDE MANUFACTURES SPECIFICATION SHEET FOR | | ALL UNDERGROUND EQUIPMENT FOR FIRE INSPECTOR REVIEW AND | | VERIFICATION AT THE TIME OF INSPECTION. | | | | | | 3) DO NOT COVER OVER PRIOR TO FIRE INSPECTION. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|