Plan Review Notes
Plan Review Notes For Permit 17050276
Permit Number 17050276
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-05-05 13:04:348264 NORTHLAKE BOULEVARD
 PERMIT #17050276
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS DO NOT INDICATE THE USE/OCCUPANCY OF THE
 STRUCTURE.
  
 PLANS DO NOT INDICATE THE CANDELA OF THE APPLIANCES OR
 CLASS/STYLE OF WIRING.
  
 PLANS INDICATE A SMOKE DETECTOR IN ONE STORAGE ROOM;
 HOWEVER, THE OTHER TWO ROOMS HAVE NO INITIATING
 DEVICES.
  
 A SINGLE HORN-STROBE DEVICE DOES NOT APPEAR TO PROVIDE
 COVERAGE IN THE LARGEST ROOM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL