Plan Review Notes For Permit 17050223 |
Permit Number |
17050223 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-07-13 16:41:09 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- INSPECTION REQUIRED FOR PROPOSED DRAINAGE PLAN. | | 2- PROVIDE CORRECT AREA CALCULATION ON SHEET A-1. | | 3- PROVIDE SURVEY W/ ORIGINAL SEAL/SIGNATURE. | | 4- REVISE CARBON MONOXIDE ALARMS LOCATION. | | 5- REVISE WINDOW/DOOR BUCK DETAILS. BEVELED BUCKS ARE | | NOT ALLOWED AND THE BUCK NEEDS TO PROVIDE FULL SUPPORT | | TO THE WINDOW/DOOR FRAME. | | 6- REVISE ENERGY CALCULATIONS: (A) COMPLETE | | INFORMATION: OWNER NAME, PERMIT OFFICE, JURISDICTION | | NUMBER (604700). (B) NEED CALCULATIONS FOR THE ACTUAL | | ORIENTATION OF THE BUILDING, NOT WORST CASE. C) MISSING | | INFORMATION ABOUT ADJACENT WALL. D) REVISE TYPE AND | | MATERIALS OF THE ROOF INFORMATION. E) REVISE DOORS | | INFORMATION. NO INSULATED DOORS. REVISE SIZE ALSO. F) | | DOORS WITH GLASS NEED TO BE CONSIDERED IN THE WINDOW | | AREA. G) REVISE THE WINDOWS INFORMATION. THE OVERHANG | | SEPARATION DOESN'T MATCH PLANS. H) PROVIDE | | MANUFACTURER'S SPECIFICATIONS SHOWING THE SPECIFIED | | U-FACTOR AND SHGC FACTOR FOR DOORS AND WINDOWS. |
|