2017-07-06 17:38:03NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR AGREES TO SUBMIT THE REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES
 WILL APPLY. CONTRACTOR TO ADVICE IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME. PERMIT WILL BE
 PROCESSED ONCE THE ENERGY CALCULATIONS ARE SIGNED BY
 THE OWNER AND THE IMPACT FEE COUNTY STAMP ON PLANS AND
 COPY OF PAID FEES ARE SUBMITTED.
  
  
 1- AREA CALCULATION ON SHEET A-1 IS INCORRECT. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE: GARAGE AREA IS INCORRECT AND THE TOTAL AREA
 IS INCORRECT ALSO. REVISE AS REQUIRED.
  
 2-ENLARGED SURVEY SUBMITTED NEEDS THE ORIGINAL SEAL AND
 SIGNATURE OF THE SURVEYOR AS REQUIRED BY CHAPTER 472
 FLORIDA STATUTE. NOTE: ENGINEER OF RECORD SIGNED AND
 SEALED THE SURVEY. HE CAN NOT SIGN AND SEAL THE SURVEY
 IF IT WAS NOT DONE BY HIM. FAC 61G15-23.002.
 RESPONSE: NO SURVEY OR SITE PLAN WAS SUBMITTED AT THIS
 TIME. NEED SURVEY OR SITE PLANS AS REQUIRED BY SEC.
 107.3.5.3 CITY AMENDMENTS.
  
 3- ENGINEER OF RECORD TO SPECIFY CARBON MONOXIDE ALARMS
 ON PLANS AS REQUIRED BY SEC. R315 FBC-RESIDENTIAL.
 RESPONSE: ENGINEER TO CHECK SEC. R315 FBC-RESIDENTIAL
 AND REVISE ALARM LOCATION ON PLANS AS REQUIRED.
  
 4- WINDOW AND DOOR BUCK DETAILS AND SPECIFICATIONS
 SHOWN ON SHEET A-1: BEVELED BUCKS ARE NOT ALLOWED AND
 THE BUCK NEEDS TO PROVIDE FULL SUPPORT TO THE WINDOW
 AND DOOR FRAME. REVISE DETAILS AND SPECIFICATIONS AS
 REQUIRED TO SHOW COMPLIANCE. SEC. R612.7.2.1
 FBC-RESIDENTIAL.
 RESPONSE: DETAILS ON SHEET A-1 SPECIFY BEVELED BUCK AND
 NEED TO PROVIDE FULL SUPPORT TO THE DOOR FRAME. SEE
 DOORS PRODUCT APPROVAL FOR SIZE OF DOOR FRAME AND
 REVISE BUCK SIZE AS REQUIRED.
  
 5- REVISE ENERGY CALCULATIONS SUBMITTED:
 ENGINEER OF RECORD RESPONSE LETTER STATED THE
 FOLLOWING; " FORMS AND CALCULATIONS ARE IN PROCESS OF
 SUBSTANTIAL REVISIONS BY OTHERS. THEREFORE, AT THIS
 TIME IT IS REQUESTED THAT THE SUBJECT IS DEFERRED FOR A
 REASONABLE TIME".
 RESPONSE: NEED REVISED ENERGY CALCULATIONS SIGNED BY
 THE OWNER OR LEGALLY DESIGNATED AGENT ARE REQUIRED
 PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 A) AFTER THE ENERGY CALCULATIONS ARE REVISED, THE OWNER
 NEEDS TO CERTIFY AT THE BOTTOM OF THE FORM AS REQUIRED
 BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: NOT ADDRESSED.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER (604700) . SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
  
 C) ENERGY CALCULATIONS SUBMITTED ARE DONE FOR THE WORST
 CASE SCENARIO. ENERGY CALCULATIONS NEED TO BE DONE FOR
 THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
  
 D) ITEM #9 IS MISSING THE INFORMATION ABOUT THE
 ADJACENT WALL SEPARATING THE GARAGE FROM THE MAIN
 HOUSE. PROVIDE COMPLETE INFORMATION. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
 RESPONSE: NOT ADDRESSED.
  
 E) THE TYPE AND MATERIALS OF THE ROOF INFORMATION ON
 PAGE 2 OF 4 IS INCORRECT. SEE PLANS AND PRODUCT
 APPROVALS AND REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
  
 F) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION. WHERE ARE THE
 INSULATED DOORS. ALSO, SIZE OF DOORS DON'T MATCH PLANS.
 SEE PLANS AND PRODUCT APPROVALS SUBMITTED AND REVISE AS
 REQUIRED TO MATCH.
 RESPONSE: NOT ADDRESSED.
  
 G) DOORS WITH GLASS NEED TO BE CONSIDERED IN THE WINDOW
 AREA AS REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY
 CONSERVATION. SEE PLANS AND PRODUCT APPROVALS SUBMITTED
 AND REVISE AS REQUIRED TO MATCH.
 RESPONSE: NOT ADDRESSED.
  
 H) REVISE THE WINDOWS INFORMATION ON PAGE 3 OF 4. THE
 OVERHANG SEPARATION DOESN'T MATCH PLANS. SEE PLANS AND
 REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
  
 I) SINCE THE ENERGY CALCULATIONS (ITEM #7) ARE USING
 WINDOWS WITH A U-FACTOR AND SHGC FACTOR OTHER THAN THE
 DEFAULT FACTOR, THEN PROVIDE MANUFACTURER'S
 SPECIFICATIONS SHOWING THE CALCULATED FACTORS FOR ALL
 DOORS AND WINDOWS. NOTE: LABEL ON THE WINDOWS AND DOORS
 WILL BE REQUIRED AT TIME OF INSPECTION.
 SEC. R405.3 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
  
 ****ADD NOTE ON PROVISO FOR INSPECTOR TO CHECK THE
 ENGINEER'S DRAINAGE PROPOSAL.
  
 NOTES:
 *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  