2017-07-06 17:38:03 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS THAT CONTRACTOR AGREES TO SUBMIT THE REQUIRED |
| INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE |
| INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES |
| WILL APPLY. CONTRACTOR TO ADVICE IN WRITING IF PROVISO |
| OPTION IS PREFERRED AT THIS TIME. PERMIT WILL BE |
| PROCESSED ONCE THE ENERGY CALCULATIONS ARE SIGNED BY |
| THE OWNER AND THE IMPACT FEE COUNTY STAMP ON PLANS AND |
| COPY OF PAID FEES ARE SUBMITTED. |
| |
| |
| 1- AREA CALCULATION ON SHEET A-1 IS INCORRECT. REVISE |
| AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| RESPONSE: GARAGE AREA IS INCORRECT AND THE TOTAL AREA |
| IS INCORRECT ALSO. REVISE AS REQUIRED. |
| |
| 2-ENLARGED SURVEY SUBMITTED NEEDS THE ORIGINAL SEAL AND |
| SIGNATURE OF THE SURVEYOR AS REQUIRED BY CHAPTER 472 |
| FLORIDA STATUTE. NOTE: ENGINEER OF RECORD SIGNED AND |
| SEALED THE SURVEY. HE CAN NOT SIGN AND SEAL THE SURVEY |
| IF IT WAS NOT DONE BY HIM. FAC 61G15-23.002. |
| RESPONSE: NO SURVEY OR SITE PLAN WAS SUBMITTED AT THIS |
| TIME. NEED SURVEY OR SITE PLANS AS REQUIRED BY SEC. |
| 107.3.5.3 CITY AMENDMENTS. |
| |
| 3- ENGINEER OF RECORD TO SPECIFY CARBON MONOXIDE ALARMS |
| ON PLANS AS REQUIRED BY SEC. R315 FBC-RESIDENTIAL. |
| RESPONSE: ENGINEER TO CHECK SEC. R315 FBC-RESIDENTIAL |
| AND REVISE ALARM LOCATION ON PLANS AS REQUIRED. |
| |
| 4- WINDOW AND DOOR BUCK DETAILS AND SPECIFICATIONS |
| SHOWN ON SHEET A-1: BEVELED BUCKS ARE NOT ALLOWED AND |
| THE BUCK NEEDS TO PROVIDE FULL SUPPORT TO THE WINDOW |
| AND DOOR FRAME. REVISE DETAILS AND SPECIFICATIONS AS |
| REQUIRED TO SHOW COMPLIANCE. SEC. R612.7.2.1 |
| FBC-RESIDENTIAL. |
| RESPONSE: DETAILS ON SHEET A-1 SPECIFY BEVELED BUCK AND |
| NEED TO PROVIDE FULL SUPPORT TO THE DOOR FRAME. SEE |
| DOORS PRODUCT APPROVAL FOR SIZE OF DOOR FRAME AND |
| REVISE BUCK SIZE AS REQUIRED. |
| |
| 5- REVISE ENERGY CALCULATIONS SUBMITTED: |
| ENGINEER OF RECORD RESPONSE LETTER STATED THE |
| FOLLOWING; " FORMS AND CALCULATIONS ARE IN PROCESS OF |
| SUBSTANTIAL REVISIONS BY OTHERS. THEREFORE, AT THIS |
| TIME IT IS REQUESTED THAT THE SUBJECT IS DEFERRED FOR A |
| REASONABLE TIME". |
| RESPONSE: NEED REVISED ENERGY CALCULATIONS SIGNED BY |
| THE OWNER OR LEGALLY DESIGNATED AGENT ARE REQUIRED |
| PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC. |
| R103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| A) AFTER THE ENERGY CALCULATIONS ARE REVISED, THE OWNER |
| NEEDS TO CERTIFY AT THE BOTTOM OF THE FORM AS REQUIRED |
| BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| RESPONSE: NOT ADDRESSED. |
| |
| B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE OWNER NAME, PERMIT OFFICE AND |
| JURISDICTION NUMBER (604700) . SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| RESPONSE: NOT ADDRESSED. |
| |
| C) ENERGY CALCULATIONS SUBMITTED ARE DONE FOR THE WORST |
| CASE SCENARIO. ENERGY CALCULATIONS NEED TO BE DONE FOR |
| THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| RESPONSE: NOT ADDRESSED. |
| |
| D) ITEM #9 IS MISSING THE INFORMATION ABOUT THE |
| ADJACENT WALL SEPARATING THE GARAGE FROM THE MAIN |
| HOUSE. PROVIDE COMPLETE INFORMATION. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| RESPONSE: NOT ADDRESSED. |
| RESPONSE: NOT ADDRESSED. |
| |
| E) THE TYPE AND MATERIALS OF THE ROOF INFORMATION ON |
| PAGE 2 OF 4 IS INCORRECT. SEE PLANS AND PRODUCT |
| APPROVALS AND REVISE AS REQUIRED TO MATCH. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| RESPONSE: NOT ADDRESSED. |
| |
| F) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. WHERE ARE THE |
| INSULATED DOORS. ALSO, SIZE OF DOORS DON'T MATCH PLANS. |
| SEE PLANS AND PRODUCT APPROVALS SUBMITTED AND REVISE AS |
| REQUIRED TO MATCH. |
| RESPONSE: NOT ADDRESSED. |
| |
| G) DOORS WITH GLASS NEED TO BE CONSIDERED IN THE WINDOW |
| AREA AS REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY |
| CONSERVATION. SEE PLANS AND PRODUCT APPROVALS SUBMITTED |
| AND REVISE AS REQUIRED TO MATCH. |
| RESPONSE: NOT ADDRESSED. |
| |
| H) REVISE THE WINDOWS INFORMATION ON PAGE 3 OF 4. THE |
| OVERHANG SEPARATION DOESN'T MATCH PLANS. SEE PLANS AND |
| REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| RESPONSE: NOT ADDRESSED. |
| |
| I) SINCE THE ENERGY CALCULATIONS (ITEM #7) ARE USING |
| WINDOWS WITH A U-FACTOR AND SHGC FACTOR OTHER THAN THE |
| DEFAULT FACTOR, THEN PROVIDE MANUFACTURER'S |
| SPECIFICATIONS SHOWING THE CALCULATED FACTORS FOR ALL |
| DOORS AND WINDOWS. NOTE: LABEL ON THE WINDOWS AND DOORS |
| WILL BE REQUIRED AT TIME OF INSPECTION. |
| SEC. R405.3 FBC-ENERGY CONSERVATION. |
| RESPONSE: NOT ADDRESSED. |
| |
| ****ADD NOTE ON PROVISO FOR INSPECTOR TO CHECK THE |
| ENGINEER'S DRAINAGE PROPOSAL. |
| |
| NOTES: |
| *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |