2017-06-02 09:25:29 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- ACCORDING TO THE ENERGY CALCULATIONS SUBMITTED, IT | | LOOKS LIKE THE EQUIPMENT SIZING CALCULATIONS WERE DONE | | BASED ON THE WORST CASE SCENARIO (SEE BUILDING REVIEW | | COMMENTS). THE EQUIPMENT SIZING NEEDS TO BE CALCULATED | | BASED ON THE ACTUAL ORIENTATION OF THE BUILDING AS | | REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH | | EDITION (2014). REVISE CALCULATIONS AND PROVIDE | | COMPLETE CALCULATIONS NOT JUST THE SUMMARY SHEET. | | | | 2- PROVIDE COMPLETE A/C PLAN. NOTE: A/C PLAN TO INCLUDE | | THE EQUIPMENT MANUFACTURER AND MODEL SPECIFIED ON THE | | EQUIPMENT SIZING CALCULATIONS. SEC. 107.3.5.3(10) CITY | | AMENDMENTS. | | | | NOTE: | | *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING | | EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|