2017-06-02 09:25:29NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- ACCORDING TO THE ENERGY CALCULATIONS SUBMITTED, IT
 LOOKS LIKE THE EQUIPMENT SIZING CALCULATIONS WERE DONE
 BASED ON THE WORST CASE SCENARIO (SEE BUILDING REVIEW
 COMMENTS). THE EQUIPMENT SIZING NEEDS TO BE CALCULATED
 BASED ON THE ACTUAL ORIENTATION OF THE BUILDING AS
 REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014). REVISE CALCULATIONS AND PROVIDE
 COMPLETE CALCULATIONS NOT JUST THE SUMMARY SHEET.
  
 2- PROVIDE COMPLETE A/C PLAN. NOTE: A/C PLAN TO INCLUDE
 THE EQUIPMENT MANUFACTURER AND MODEL SPECIFIED ON THE
 EQUIPMENT SIZING CALCULATIONS. SEC. 107.3.5.3(10) CITY
 AMENDMENTS.
  
 NOTE:
 *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  