2017-05-11 12:50:231ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050212
 5/11/17
  
 1) PROVIDE A PLAN THAT SHOWS THE LOCATION OF THE
 CONDENSER ON THE ROOF, INDICATE THE FUNCTION OF THE
 CONDENSER, AND PROVIDE AN EQUIPMENT SCHEDULE.
  
 2) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING THE
 CONDENSER TO THE ROOF STRUCTURE- SECTION 301.15.
  
 3) BECAUSE THIS IS A SEPARATE PERMIT FROM THE PRIMARY,
 THE MECHANICAL CONTRACTOR MUST SUBMIT A COMPLETE PERMIT
 APPLICATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719