Plan Review Notes
Plan Review Notes For Permit 17050163
Permit Number 17050163
Review Stop R
Sequence Number 1
Notes
Date Text
2017-05-30 07:33:59 
 1-FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R3
 SUBMITTED:
 A) SELECTED ASSEMBLY (W-1) IS FOR AN INSULATED FLAT
 ROOF ASSEMBLY. PLANS SUBMITTED DON'T SPECIFIED
 INSULATED FLAT ROOF ASSEMBLY. CLARIFY IF INSTALLING
 INSULATED ASSEMBLY OR NON-INSULATED ASSEMBLY. REVISE
 PLANS AND SELECTED ASSEMBLY AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) THERE IS A HANDWRITTEN NOTE ON PAGE 4 OF 14 ON THE
 SELECTED ASSEMBLY (W-1) SPECIFYING 1/8" / FT. SLOPE
 TAPERED PERLITE INSULATION. SEC. R905.11.1
 FBC-RESIDENTIAL AND SECOND FLOOR ROOF PLAN ON SHEET
 A-2.1 REQUIRES 1/4" PER FT MINIMUM ROOF SLOPE. REVISE
 AS REQUIRED.
  
 C) INFORMATION SHOWN ON RAS 117 CALCULATIONS PREPARED
 BY TURQUOISE ENGINEERING AND FLORIDA PRODUCT APPROVAL
 FL16709-R3 SUBMITTED DON'T MATCH. ENGINEER CALCULATIONS
 ARE REFERING TO APPROVED ASSEMBLY W-3 WHILE FLORIDA
 PRODUCT APPROVAL SUBMITTED IS FOR APPROVED ASSEMBLY
 W-1. REVISE AS REQUIRED TO MATCH AND COORDINATE WITH
 ITEM #1(A) ABOVE. SEC. 107.2.1 CITY AMENDMENTS.