Plan Review Notes For Permit 17050163 |
Permit Number |
17050163 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-31 13:46:12 | | | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014) | | | | 1- PLANS SUBMITTED ARE TOO SMALL . UNABLE TO READ THEM. | | NEED TO PROVIDE PLANS DRAWN TO A MINIMUM 1/8 INCH | | SCALE. PROVIDE 2 COPIES. SEC. 107.1 AND 107.2.1.4 CITY | | AMENDMENTS. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD | | DRAWINGS FOR REFERENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|