2017-05-30 07:37:2905/31/17 ACCORDING TO PLANS ON PERMIT #04070599 THIS
 PROPERTY IS FOR ONE SINGLE FAMILY RESIDENCE ONLY. NOT
 COMMERCIAL USE. NOT TENANT SEPARATION REQUIRED.
  
  
 RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- AFTER PLANS ARE REVISED (SEE ZONING COMMENTS) BRING
 THEM TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT
 FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND
 COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- INFORMATION SHOWN ON WALL SECTION 3 ON SHEET A-2.1
 DOESN'T MATCH INFORMATION SHOWN ON WALL SECTION "A" AND
 ON ROOF SHEATHING AND WALL SHEATHING NOTES SHOWN ON
 SHEET S-1. REVISE PLYWOOD SHEATHING THICKNESS TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- ROOF SHEATHING NOTE ON SHEET S-1: SEC. R803.2.3.1
 FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS. ROOF
 SHEATHING NOTE ON SHEET S-1 SPECIFIES 6D NAILS.
 ENGINEER OF RECORD TO PROVIDE CALCULATIONS (BASED ON
 THE HEIGHT AND BUILDING EXPOSURE "D" OF THIS BUILDING)
 SHOWING THAT THE PROPOSED ROOF SHEATHING NAIL TYPE,
 SIZE AND SPACING IS EQUAL OR BETTER THAN THE
 SPECIFICATIONS REQUIRED BY SEC. R803.2.3.1.
  
 4- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R3
 SUBMITTED:
 A) SELECTED ASSEMBLY (W-1) IS FOR AN INSULATED FLAT
 ROOF ASSEMBLY. PLANS SUBMITTED DON'T SPECIFIED
 INSULATED FLAT ROOF ASSEMBLY. CLARIFY IF INSTALLING
 INSULATED ASSEMBLY OR NON-INSULATED ASSEMBLY. REVISE
 PLANS AND SELECTED ASSEMBLY AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) THERE IS A HANDWRITTEN NOTE ON PAGE 4 OF 14 ON THE
 SELECTED ASSEMBLY (W-1) SPECIFYING 1/8" / FT. SLOPE
 TAPERED PERLITE INSULATION. SEC. R905.11.1
 FBC-RESIDENTIAL AND SECOND FLOOR ROOF PLAN ON SHEET
 A-2.1 REQUIRES 1/4" PER FT MINIMUM ROOF SLOPE. REVISE
 AS REQUIRED.
  
 C) INFORMATION SHOWN ON RAS 117 CALCULATIONS PREPARED
 BY TURQUOISE ENGINEERING AND FLORIDA PRODUCT APPROVAL
 FL16709-R3 SUBMITTED DON'T MATCH. ENGINEER CALCULATIONS
 ARE REFERRING TO APPROVED ASSEMBLY W-3 WHILE FLORIDA
 PRODUCT APPROVAL SUBMITTED IS FOR APPROVED ASSEMBLY
 W-1. REVISE AS REQUIRED TO MATCH AND COORDINATE WITH
 ITEM #4(A) ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- REVISE ENERGY CALCULATIONS SUBMITTED;
 A) PROVIDE COMPLETE INFORMATION ON TOP OF THE FORM,
 INCLUDING THE NAME OF THE BUILDER. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) REVISE THE CEILING INFORMATION ON ITEM #10 TO MATCH
 PLANS SUBMITTED. PLANS CALL FOR A VENTED CEILING NOT
 UNVENTED. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) REVISE THE WINDOWS INFORMATION ON PAGE 3 OF 4 TO
 MATCH PLANS. THERE ARE NOT TWO WINDOWS ON THE SW WALL.
 SEE PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) REVISE THE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4.
 SEE PLANS AND PRODUCT APPROVAL AND REVIEW AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 ATTACHMENT OF THE A/C CONDENSER UNIT AS SPECIFIED ON
 SECOND FLOOR PLAN ON SHEET A-2.1. EQUIPMENT NEEDS TO BE
 FASTENED TO RESIST THE WIND LOADS OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: KEEP IN MIND THAT EXTERIOR WALLS
 FRAMING IS STEEL STUDS.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  