2017-05-15 14:05:23 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1. TYPICAL WALL SECTION ON PLAN PAGE A-1 DENOTES THE |
| INSTALLATION OF 5/8" STUCCO. PROVIDE A WATER RESISTIVE |
| BARRIER PER R703.6.3 WHEN INSTALLING THE REQUIRED METAL |
| LATH. |
| 2. PROVIDE A FASTENER SCHEDULE FOR THE CONNECTION OF |
| NEW WOOD FRAMED WALLS TO EXISTING CONCRETE COLUMNS. |
| |
| R703.6.3 WATER-RESISTIVE BARRIERS. |
| WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED |
| IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED |
| SHEATHING, SHALL INCLUDE A WATER-RESISTIVE |
| VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST |
| EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE |
| INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH |
| THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE |
| AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION |
| R703.8) INTENDED TO DRAIN TO THE WATER-RESISTIVE |
| BARRIER IS DIRECTED BETWEEN THE LAYERS. |
| |