2017-05-11 11:21:00 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE SHUTTER SCHEDULE. YOU MAY USE THE CITY OF |
| WEST PALM BEACH SCHEDULE FOR INSTALLATION OF OPENING |
| PROTECTIVE DEVICES AND ASSEMBLIES. |
| |
| FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-R301.2. |
| |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF |
| THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND |
| DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1. |
| WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL |
| MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING, |
| THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH |
| PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE |
| WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR |
| HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED |
| TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR |
| WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR |
| WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN |
| GARAGE DOORS). |
| |