2017-05-24 13:25:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) THERE ARE NO PLAN SHEETS SUBMITTAL THAT INDICATES |
| LOCATION AND OR COMPLAINCE WITH ANY FIRE CODE. |
| |
| PLEASE PROVIDE DETAILED FLOOR PLAN SHEETS INDICATING |
| LOCATION OF THE GENERATOR AND THE LOCATION AND |
| IDENTIFICATION OF EACH PIECE OF EQUIPMENT IN THE ROOM. |
| |
| |
| |
| 2) THERE IS NO SCOPE OF WORK SUBMITTED. |
| |
| |
| PLEASE A DETAILED PROVIDE THE SCOPE OF WORK UNDER THIS |
| PERMIT. |
| |
| |
| |
| 3) THIS APPEARS TO BE AN EMERGENCY GENERATOR THAT |
| PROVIDES EMERGENCY POWER TO THE LIFE SAFETY FEATURES OF |
| THE BUILDING. |
| |
| IF SO, IT SHALL COMPLY WITH NFPA 110, STANDARD FOR |
| EMERGENCY AND STANDBY POWER SYSTEMS. |
| |
| PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE |
| INDICATING NOTE OF THE PLAN SHEETS. |
| |
| |
| |
| |
| 4) THE EMERGENCY GENERATOR SHALL BE TIED INTO THE FIRE |
| COMMAND ROOM. THE FIRE COMMAND CENTER SHALL COMPLY WITH |
| NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL |
| CONTAIN, BUT NOT LIMITED TO, THE FOLLOWING FEATURES: |
| |
| 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| |
| 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| TRANSFER FEATURES. |
| |
| 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| PROVIDED |
| |
| PLEASE ENSURE COMPLAINCE AND PROVIDE AN APPLICABLE NOTE |
| OF COMPLIANCE ON THE PLAN SHEETS. |
| |
| |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |