Plan Review Notes
Plan Review Notes For Permit 17050035
Permit Number 17050035
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-05-24 13:25:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO PLAN SHEETS SUBMITTAL THAT INDICATES
 LOCATION AND OR COMPLAINCE WITH ANY FIRE CODE.
  
 PLEASE PROVIDE DETAILED FLOOR PLAN SHEETS INDICATING
 LOCATION OF THE GENERATOR AND THE LOCATION AND
 IDENTIFICATION OF EACH PIECE OF EQUIPMENT IN THE ROOM.
  
  
  
 2) THERE IS NO SCOPE OF WORK SUBMITTED.
  
  
 PLEASE A DETAILED PROVIDE THE SCOPE OF WORK UNDER THIS
 PERMIT.
  
  
  
 3) THIS APPEARS TO BE AN EMERGENCY GENERATOR THAT
 PROVIDES EMERGENCY POWER TO THE LIFE SAFETY FEATURES OF
 THE BUILDING.
  
 IF SO, IT SHALL COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE
 INDICATING NOTE OF THE PLAN SHEETS.
  
  
  
  
 4) THE EMERGENCY GENERATOR SHALL BE TIED INTO THE FIRE
 COMMAND ROOM. THE FIRE COMMAND CENTER SHALL COMPLY WITH
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL
 CONTAIN, BUT NOT LIMITED TO, THE FOLLOWING FEATURES:
  
 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS
  
 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
  
 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
  
 PLEASE ENSURE COMPLAINCE AND PROVIDE AN APPLICABLE NOTE
 OF COMPLIANCE ON THE PLAN SHEETS.
  
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  