2017-05-02 11:21:261ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041240
 5/2/17
  
 1) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SHOW COMPLIANCE WITH C403.2.7.5 FBC-14 ENERGY
 CONSERVATION CODE FOR AIR DISTRIBUTION, AND DUCT SYSTEM
 SIZING.
  