Plan Review Notes
Plan Review Notes For Permit 17041233
Permit Number 17041233
Review Stop E
Sequence Number 3
Notes
Date Text
2017-09-19 14:08:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ATTACHED THE FOLLOWING ITEMS TO PLAN AS PROVISO:
  
 MAIN HOUSE:
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 2. MAIN BREAKER REQUIRED AT SERVICE FOR EACH PANEL.
 PROVIDE CORRECTION. NEC 230.70(A); FBC RE 3601.6.2
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 4. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE 6 FEET AWAY OR PROVIDE EVIDENCE OF
 RESISTANCE TO GROUND OF 25 OHMS OR LESS. NEC 250.56;
 FBC RE 3608.4
 5. INCLUDE ALL GROUNDING ELECTRODES PRESENT TO BE
 BONDED AT SERVICE. NEC 250.50; FBC RE 3608.1
 6. SMOKE/CO ALARMS OUTSIDE OF BEDROOM SHOULD BE IN THE
 IMMEDIATE VICINITY OF THE SLEEPING ROOM AND INSTALLED
 AT THE HIGHEST POINT IN THE ROOM, AT LEAST 3 FEET FROM
 ANY MECHANICAL VENT OR CEILING FAN. PROVIDE CORRECTION.
 FBC RE 314.3; NFPA 72; 11.8.3.5
 7. LOAD CALCULATION FOR SERVICE SHOULD INCLUDE ALL
 LOADS, INCLUDING THE DETACHED GARAGE. A DISPOSAL IS NOT
 INCLUDED IN THE GENERAL LIGHTING LOAD. PROVIDE
 CORRECTED LOAD CALCULATION. NEC 220.82; FBC RE 3602.2
 DETACHED GARAGE:
 8. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 9. PROVIDE GROUNDING ELECTRODE SYSTEM AT DETACHED
 GARAGE AS REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED
 BY A FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3
 10. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER FOR PANEL IN DETACHED GARAGE IN ADDITION
 TO THE MAIN BREAKER FEEDING THE PANEL. PANEL MUST BE
 SIZED FOR MAIN BREAKER FEEDING THIS PANEL FROM SERVICE.
 NEC 225.31, 225.32; FBC RE 3706.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER