2017-09-19 14:08:13 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ATTACHED THE FOLLOWING ITEMS TO PLAN AS PROVISO: |
| |
| MAIN HOUSE: |
| 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC |
| RE3706.2, RE3902 |
| 2. MAIN BREAKER REQUIRED AT SERVICE FOR EACH PANEL. |
| PROVIDE CORRECTION. NEC 230.70(A); FBC RE 3601.6.2 |
| 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. NEC 250.94; FBC RE3609.3 |
| 4. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN |
| ADDITIONAL ELECTRODE 6 FEET AWAY OR PROVIDE EVIDENCE OF |
| RESISTANCE TO GROUND OF 25 OHMS OR LESS. NEC 250.56; |
| FBC RE 3608.4 |
| 5. INCLUDE ALL GROUNDING ELECTRODES PRESENT TO BE |
| BONDED AT SERVICE. NEC 250.50; FBC RE 3608.1 |
| 6. SMOKE/CO ALARMS OUTSIDE OF BEDROOM SHOULD BE IN THE |
| IMMEDIATE VICINITY OF THE SLEEPING ROOM AND INSTALLED |
| AT THE HIGHEST POINT IN THE ROOM, AT LEAST 3 FEET FROM |
| ANY MECHANICAL VENT OR CEILING FAN. PROVIDE CORRECTION. |
| FBC RE 314.3; NFPA 72; 11.8.3.5 |
| 7. LOAD CALCULATION FOR SERVICE SHOULD INCLUDE ALL |
| LOADS, INCLUDING THE DETACHED GARAGE. A DISPOSAL IS NOT |
| INCLUDED IN THE GENERAL LIGHTING LOAD. PROVIDE |
| CORRECTED LOAD CALCULATION. NEC 220.82; FBC RE 3602.2 |
| DETACHED GARAGE: |
| 8. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC |
| RE3706.2, RE3902 |
| 9. PROVIDE GROUNDING ELECTRODE SYSTEM AT DETACHED |
| GARAGE AS REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED |
| BY A FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3 |
| 10. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| MAIN BREAKER FOR PANEL IN DETACHED GARAGE IN ADDITION |
| TO THE MAIN BREAKER FEEDING THE PANEL. PANEL MUST BE |
| SIZED FOR MAIN BREAKER FEEDING THIS PANEL FROM SERVICE. |
| NEC 225.31, 225.32; FBC RE 3706.3 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |