Plan Review Notes
Plan Review Notes For Permit 17041226
Permit Number 17041226
Review Stop P
Sequence Number 1
Notes
Date Text
2017-06-09 11:17:211) SHT. P312B - THE GAS LINE CHANGES PIPE SIZE FROM 1
 1/4" TO 2" UP TO A FIRE PIT. SEE GAS LINE ON GRIDLINE
 E.0 BETWEEN GRIDLINE 12-13. CLARIFY. THIS DOES NOT
 CORRELATE WITH THE RISER ON SHT. P717.
 2) SHT. P312B - SHOWS AN 1 1/4 " GAS LINE SUPPLYING A
 2" GAS LINE UP TO A FIRE PIT. CLARIFY. REFER TO GAS
 LINE BETWEEN GRIDLINES F.1 - G AND 11 - 12. THIS DOES
 NOT CORRELATE WITH THE RISER ON SHT. P717.
 3) SHT. P312B - THERE IS AN 1 1/2" GAS LINE BEING FEED
 FROM A 2 1/2 " GAS LINE. SEE GRIDLINES 10 -11 ON A
 LINE. THIS DOES NOT CORRELATE WITH THE RISER ON SHT.
 P717.
 4) THE NARRATIVE STATES THAT FIRE PITS HAVE BEEN
 DELETED BUT THE GAS DRAWINGS STILL CALL OUT AND SHOWS
 GAS PIPING TO THE FIRE PITS. CLARIFY.
 5) SHT. P313B - THE NARRATIVE NOTES THAT THE NATURAL
 GAS TO THE FIRE PITS HAS BEEN DELETED AND GAS TO THE
 FIRE TABLES HAS BEEN ADDED BUT THE FIRE PITS ARE STILL
 NOTED/SHOWN ON THE PLANS AND THE FIRE TABLES ARE NOT
 SHOWN ON THE PLANS. CLARIFY.
 6) SHT. P717 - SHOW THE TOTAL DEVELOPED LENGTH FROM THE
 OUTLET OF THE GAS METER TO THE MOST REMOTE OUTLET ON
 THE SYSTEM.FBC-FUEL GAS SEC. 402.4.1.
 7) SHT. P717 - THE NARRATIVE FOR THIS SHEET NOTES THE
 DELETION OF GAS TO THE FIRE PITS AND ADDING GAS TO THE
 FIRE TABLES BUT THE FIRE PITS ARE STILL SHOWN ON THE
 GAS RISER AND THERE ARE NO FIRE TABLES SHOWN. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  