Plan Review Notes For Permit 17041226 |
Permit Number |
17041226 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-18 12:37:37 | 1ST REVIEW FBC-2014 MECHANICAL | | REVISION PERMIT #17041226 | | MASTER #16070715 | | 5/18/17 | | | | RESULTS: DENIED | | | | PLEASE ADDRESS THE COMMENTS LISTED BELOW. | | | | 1) SHEET M201: IN ACCORDANCE WITH SECTION 7.7.2.3 NFPA | | 110, THE FIRE DAMPER CANNOT BE INSTALLED TO PROTECT THE | | O/A GENERATOR INTAKE OPENING. | | | | 2) SHEETS M204, 206, 207, 210, 211, 212: PROVIDE A | | CALCULATION AND A MEANS OF PROVIDING OUTSIDE AIR TO THE | | NEW FCU'S SERVING THE NEW ELEVATOR LOBBIES. | | | | 3) M206: A MINIMUM 10' CLEARANCE IS REQUIRED BETWEEN | | THE O/A INTAKE AND EXHAUST OPENINGS AT THE FPL VAULT. | | PLEASE VERIFY WITH MEASUREMENTS ON THE PLAN- SECTION | | 401.4. | | | | 4) M210: THE NEW CU-2-2 IS MISLABELED AS CU-2-3 ON THE | | EAST LINER ROOF. | | | | 5) M212: PROVIDE AN FSD AT THE PENETRATION OF THE | | PRESSURIZATION DUCT AT STAIR #3. | | | | 6) M213: SHOW THE 12X8 O/A DUCT DROP AND FSD PER NOTE | | #3. PROVIDE A SUBMITTAL FOR THE FIRE WRAP. | | | | 7) M214: PROVIDE AN FSD SYMBOL AT THE 20X10 EXHAUST | | DUCT DROP PER NOTE #2 ON THE PLAN. | | | | 8) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | NEW FCU'S- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. | | | | 9) REVISE THE ENERGY CALCULATIONS TO INCLUDE THE NEW | | FCU'S. | | | | | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|