2017-05-18 12:37:371ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #17041226
 MASTER #16070715
 5/18/17
  
 RESULTS: DENIED
  
 PLEASE ADDRESS THE COMMENTS LISTED BELOW.
  
 1) SHEET M201: IN ACCORDANCE WITH SECTION 7.7.2.3 NFPA
 110, THE FIRE DAMPER CANNOT BE INSTALLED TO PROTECT THE
 O/A GENERATOR INTAKE OPENING.
  
 2) SHEETS M204, 206, 207, 210, 211, 212: PROVIDE A
 CALCULATION AND A MEANS OF PROVIDING OUTSIDE AIR TO THE
 NEW FCU'S SERVING THE NEW ELEVATOR LOBBIES.
  
 3) M206: A MINIMUM 10' CLEARANCE IS REQUIRED BETWEEN
 THE O/A INTAKE AND EXHAUST OPENINGS AT THE FPL VAULT.
 PLEASE VERIFY WITH MEASUREMENTS ON THE PLAN- SECTION
 401.4.
  
 4) M210: THE NEW CU-2-2 IS MISLABELED AS CU-2-3 ON THE
 EAST LINER ROOF.
  
 5) M212: PROVIDE AN FSD AT THE PENETRATION OF THE
 PRESSURIZATION DUCT AT STAIR #3.
  
 6) M213: SHOW THE 12X8 O/A DUCT DROP AND FSD PER NOTE
 #3. PROVIDE A SUBMITTAL FOR THE FIRE WRAP.
  
 7) M214: PROVIDE AN FSD SYMBOL AT THE 20X10 EXHAUST
 DUCT DROP PER NOTE #2 ON THE PLAN.
  
 8) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW FCU'S- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 9) REVISE THE ENERGY CALCULATIONS TO INCLUDE THE NEW
 FCU'S.
  
  
  