Plan Review Notes
Plan Review Notes For Permit 17041226
Permit Number 17041226
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-05-19 13:52:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1 ) SHEET M201 - GENERATOR ROOM - IT APPEARS THAT THE
 DUCTING, INTAKE AND EXHAUST DOES NOT MEET THE
 REQUIRMENTS OF NFPA 110, EMERGENCY AND STANDBY POWER
 SYSTEMS. CHAPTER 7, INSTALLATION AND ENVIRONMENTAL
 CONSIDERATIONS
  
 THERE APPEARS TO BE A DAMPER WITHIN THE 2 HR INTERIOR
 WALL, RADIATOR INTAKE.
  
 7.7.2.1 FOR EPS SUPPLYING LEVEL 1 EPSS, VENTILATION AIR
 SHALL BE SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE THE
 BUILDING BY AN EXTERIOR WALL OPENING OR FROM A SOURCE
 OUTSIDE THE BUILDING BY A 2-HOUR FIRE-RATED AIR
 TRANSFER SYSTEM.
 7.7.2.2 FOR EPS SUPPLYING LEVEL 1 EPSS, DISCHARGE AIR
 SHALL BE DIRECTED OUTSIDE THE BUILDING BY AN EXTERIOR
 WALL OPENING OR TO AN EXTERIOR OPENING BY A 2-HOUR
 FIRE-RATED AIR TRANSFER SYSTEM.
 7.7.2.3 FIRE DAMPERS, SHUTTERS, OR OTHER SELF-CLOSING
 DEVICES SHALL NOT BE PERMITTED IN VENTILATION OPENINGS
 OR DUCTWORK FOR SUPPLY OR RETURN/DISCHARGE AIR TO EPS
 EQUIPMENT FOR LEVEL 1 EPSS.
 7.7.3 VENTILATION AIR SUPPLY SHALL BE FROM OUTDOORS OR
 FROM A SOURCE OUTSIDE THE BUILDING BY AN EXTERIOR WALL
 OPENING OR FROM A SOURCE OUTSIDE THE BUILDING BY A
 2-HOUR FIRE-RATED AIR TRANSFER SYSTEM.
 7.7.4 VENTILATION AIR SHALL BE PROVIDED TO SUPPLY AND
 DISCHARGE COOLING AIR FOR RADIATOR COOLING OF THE EPS
 WHEN RUNNING AT RATED LOAD.
  
 7.7.4.1 VENTILATION AIR SUPPLY AND DISCHARGE FOR
 RADIATOR-COOLED EPS SHALL HAVE A MAXIMUM STATIC
 RESTRICTION OF 125 PA (0.5 IN. OF WATER COLUMN) IN THE
 DISCHARGE DUCT AT THE RADIATOR OUTLET.
  
 7.7.4.2 RADIATOR AIR DISCHARGE SHALL BE DUCTED OUTDOORS
 OR TO AN EXTERIOR OPENING BY A 2-HOUR RATED AIR
 TRANSFER SYSTEM.
  
 7.7.5 MOTOR-OPERATED DAMPERS, WHEN USED, SHALL BE
 SPRING OPERATED TO OPEN AND MOTOR CLOSED. FIRE DAMPERS,
 SHUTTERS, OR OTHER SELF-CLOSING DEVICES SHALL NOT BE
 PERMITTED IN VENTILATION OPENINGS OR DUCTWORK FOR
 SUPPLY OR RETURN/DISCHARGE AIR TO EPS EQUIPMENT FOR
 LEVEL 1 EPSS.
  
 PLEASE REVIEW, CLARIFY AND/OR CORRECT.
  
  
  
  
  
 2) SHEET M201 - GENERATOR ROOM - THERE APPEARS TO BE AN
 INTAKE FROM THE GENERATOR ROOM INTO THE THE FIRE PUMP
 ROOM THROUGH A RATED WALL.
  
 7.2 LOCATION.
 7.2.1 THE EPS SHALL BE INSTALLED IN A SEPARATE ROOM FOR
 LEVEL 1 INSTALLATIONS. EPSS EQUIPMENT SHALL BE
 PERMITTED TO BE INSTALLED IN THIS ROOM.
 7.2.1.1 THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE
 RATING OR BE LOCATED IN AN ADEQUATE ENCLOSURE LOCATED
 OUTSIDE THE BUILDING CAPABLE OF RESISTING THE ENTRANCE
 OF SNOW OR RAIN AT A MAXIMUM WIND VELOCITY REQUIRED BY
 LOCAL BUILDING CODES.
 7.2.1.2 NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL
 APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE,
 SHALL BE PERMITTED IN THIS ROOM.
  
 THE PROPOSED IN NOT RELATED TO THE USE OF THE THIS ROOM
 OR ITS EQUIPMENT. PLEASE ALSO REVIEW/PROVIDE
 MANUFACTURES SPEC SHEETS FOR APPLICABLILITY.
  
 PLEASE REVIEW, CLARIFY AND/OR CORRECT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  