Plan Review Notes For Permit 17041200 |
Permit Number |
17041200 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-24 08:44:12 | PLAN DENIED | | 1) PLEASE SHOW LOCATION OF RETURN AIR ON A/C # 2 | | PER SECTION 107 FBC | | 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR | | EXCEPTION # 3 FOR STORAGE ROOM A/C #2 RESIDENTIAL CODE | | 2014 . | | 3) REFER TO SECTION M1602.2 PROHIBITED SOURCE # 4 | | RESIDENTIAL CODE 2014 | | 4) PROVIDE SEER OF EQUIPMENT ON EQUIPMENT SCHEDULE | | ON THE PLAN. PER SECTION 107 FBC | | | | PLAN REVIEW BY HAROLD MOSER. | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|