2017-05-25 09:33:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SITE PLAN AND SURVEY DO NOT MATCH. FBC 107.2.1
 ZONING COMMENTS MUST BE ADDRESSED.
  
 2) SPECIFY THE ROOF SHEATHING AND FASTENING
 REQUIREMENTS ON THE PLANS. FBC-R803.2 AND 803.2.3.1
  
 3) CLARIFY THE EXPOSURE CATEGORY THAT IS LISTED ON
 SHEET S000. IT IS NOT CLEAR ON THE PLANS IF IT IS D OR
 C. FBC-R301.2.1.4
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. SUBMIT TWO SETS OF
 PRODUCT APPROVALS FOR THE EXTERIOR METAL LOUVER PANELS
 AND DOORS OR REQUEST THAT THE SUBMITTALS FOR THEM BE
 DEFERRED TO A LATER TIME.
  
 5) THE PRODUCT APPROVAL SUBMITTALS FOR THE ROOF
 COVERING MATERIALS HAVE NOT BEEN REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD. FBC 107.3.4
  
 6) SPECIFY THE FASTENER SPACING AND NUMBER OF ROWS FOR
 THE PERIMETER AND CORNER AREAS BY CIRCLING THE
 APPROPRIATE ITEMS FROM THE TABLES IN THE PRODUCT
 APPROVAL FOR THE MODIFIED BITUMEN FOR THE FLAT ROOFS.
 FBC 905.11.3
  
 7) THE ENERGY COMPLIANCE FORMS SPECIFY R-30 INSULATION
 IN THE ATTIC OF THE FAMILY AND KITCHEN. IT APPEARS FROM
 THE PLAN ELEVATIONS AND CROSS SECTIONS THAT THE ENTIRE
 STRUCTURE HAS SINGLE ASSEMBLY ROOF/CEILING WITH NO
 ATTIC. PLEASE CLARIFY OR REVISE PLANS TO SHOW THE ATTIC
 SPACE. FBC 107.2.1
  
 8) THE ENERGY FORMS SPECIFY THAT THIS IS NEW
 CONSTRUCTION AND IT IS A RENOVATION. FBC ENERGY
 CONSERVATION R405
  
 9) THE ENERGY FORMS SPECIFY THE WALLS TYPE AS CONCRETE
 BLOCK WITH R-6 INSULATION AND MOST OF THEM ARE 2 X 4
 WOOD FRAME. FBC ENERGY CONSERVATION R405
  
 10) THE ENERGY FORMS SPECIFY THAT THE COOLING FOR
 SYSTEM 1 IS 47.5 KBTUS. THE PLANS SPECIFY 36,500 BTUS (
 3 TON ) AND THE EQUIPMENT SIZING CALCULATIONS HAS
 36,300 BTUS ( 3 TONS ). PLEASE CLARIFY THE ENERGY FORM
 AND THE OTHER DOCUMENTS. FBC ENERGY CONSERVATION
 R403.6.1.1
  
 11) PROVIDE EXTERIOR WALL SECTIONS FOR THE VARIOUS
 EXTERIOR WALL TYPES AND IN-FILL WHICH SPECIFIES THE
 INTERIOR / EXTERIOR WALL COVERINGS, FINISHES AND
 INSULATION. FBC 107.2.1
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  