2017-05-25 09:33:51 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE SITE PLAN AND SURVEY DO NOT MATCH. FBC 107.2.1 |
| ZONING COMMENTS MUST BE ADDRESSED. |
| |
| 2) SPECIFY THE ROOF SHEATHING AND FASTENING |
| REQUIREMENTS ON THE PLANS. FBC-R803.2 AND 803.2.3.1 |
| |
| 3) CLARIFY THE EXPOSURE CATEGORY THAT IS LISTED ON |
| SHEET S000. IT IS NOT CLEAR ON THE PLANS IF IT IS D OR |
| C. FBC-R301.2.1.4 |
| |
| 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL |
| MULLIONS AND EXTERIOR DOOR TYPES. SUBMIT TWO SETS OF |
| PRODUCT APPROVALS FOR THE EXTERIOR METAL LOUVER PANELS |
| AND DOORS OR REQUEST THAT THE SUBMITTALS FOR THEM BE |
| DEFERRED TO A LATER TIME. |
| |
| 5) THE PRODUCT APPROVAL SUBMITTALS FOR THE ROOF |
| COVERING MATERIALS HAVE NOT BEEN REVIEWED AND APPROVED |
| IN WRITING BY THE DESIGNER OF RECORD. FBC 107.3.4 |
| |
| 6) SPECIFY THE FASTENER SPACING AND NUMBER OF ROWS FOR |
| THE PERIMETER AND CORNER AREAS BY CIRCLING THE |
| APPROPRIATE ITEMS FROM THE TABLES IN THE PRODUCT |
| APPROVAL FOR THE MODIFIED BITUMEN FOR THE FLAT ROOFS. |
| FBC 905.11.3 |
| |
| 7) THE ENERGY COMPLIANCE FORMS SPECIFY R-30 INSULATION |
| IN THE ATTIC OF THE FAMILY AND KITCHEN. IT APPEARS FROM |
| THE PLAN ELEVATIONS AND CROSS SECTIONS THAT THE ENTIRE |
| STRUCTURE HAS SINGLE ASSEMBLY ROOF/CEILING WITH NO |
| ATTIC. PLEASE CLARIFY OR REVISE PLANS TO SHOW THE ATTIC |
| SPACE. FBC 107.2.1 |
| |
| 8) THE ENERGY FORMS SPECIFY THAT THIS IS NEW |
| CONSTRUCTION AND IT IS A RENOVATION. FBC ENERGY |
| CONSERVATION R405 |
| |
| 9) THE ENERGY FORMS SPECIFY THE WALLS TYPE AS CONCRETE |
| BLOCK WITH R-6 INSULATION AND MOST OF THEM ARE 2 X 4 |
| WOOD FRAME. FBC ENERGY CONSERVATION R405 |
| |
| 10) THE ENERGY FORMS SPECIFY THAT THE COOLING FOR |
| SYSTEM 1 IS 47.5 KBTUS. THE PLANS SPECIFY 36,500 BTUS ( |
| 3 TON ) AND THE EQUIPMENT SIZING CALCULATIONS HAS |
| 36,300 BTUS ( 3 TONS ). PLEASE CLARIFY THE ENERGY FORM |
| AND THE OTHER DOCUMENTS. FBC ENERGY CONSERVATION |
| R403.6.1.1 |
| |
| 11) PROVIDE EXTERIOR WALL SECTIONS FOR THE VARIOUS |
| EXTERIOR WALL TYPES AND IN-FILL WHICH SPECIFIES THE |
| INTERIOR / EXTERIOR WALL COVERINGS, FINISHES AND |
| INSULATION. FBC 107.2.1 |
| |
| 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |