Plan Review Notes For Permit 17041172 |
Permit Number |
17041172 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-02 09:43:02 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | PERMIT #17041172 | | 5/2/17 | | | | 1) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING | | BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3 | | FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES | | THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. | | | | 2) PROVIDE VENTILATION FOR THE NEW STORAGE CLOSET AND | | CORRIDOR- TABLE 403.3 | | | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|