Plan Review Notes For Permit 17041172 |
Permit Number |
17041172 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-01 10:58:20 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) SHEET A 1.0 & E 1 - ALL FIRE ALARM WORK SHALL BE | | DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE | | SAFETY CONTRACTORS. | | | | | | | | 2) SHEET E 0 - THERE ARE INCORRECT REFERENCES TO THE | | CURRENT EDITIONS OF NFPA . | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | APPLICABLE CODES OR STANDARDS. | | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | NFPA 72, 2010 EDITION. | | | | PLEASE ENSURE COMPLIANCE AND UPDATE YOUR RECORDS. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|