 C405.5 INTERIOR LIGHTING POWER REQUIREMENTS
 (PRESCRIPTIVE).
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2.
  
 110.24 AVAILABLE FAULT CURRENT. (A) FIELD MARKING.
 SERVICE EQUIPMENT IN OTHER THAN DWELLING UNITS SHALL BE
 LEGIBLY MARKED IN THE FIELD WITH THE MAXIMUM AVAILABLE
 FAULT CURRENT. THE FIELD MARKLNG(S)
 SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION
 WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO
 WITHSTAND THE ENVIRONMENT INVOLVED.
  
 (B) MODIFICATIONS. WHEN MODIFICATIONS TO THE ELECTRICAL
 INSTALLATION OCCUR THAT AFFECT THE MAXIMUM AVAILABLE
 FAULT CURRENT AT THE SERVICE, THE MAXIMUM AVAILABLE
 FAULT CURRENT
 SHALL BE VERIFIED OR RECALCULATED AS NECESSARY TO
 ENSURE THE SERVICE EQUIPMENT RATINGS ARE SUFTICIENT FOR
 THE MAXIMUM AVAILABLE FAULT CULTENT AT THE LINE
 TERMINALS OF THE EQUIPMENT.
 THE REQUIRED FIELD MARKING(S) IN LLO.24(A) SHALL BE
 ADJUSTED TO REFLECT THE NEW LEVEL OF MAXIMUM AVAILABLE
 FAULT CURRENT
  
 408.4 FIELD IDENTIFICATION REQUIRED. (B) SOURCE OF
 SUPPLY. ALL SWITCHBOARDS,SWITEHGEAR, AND PANELBOARDS
 SUPPLIED BY A FEEDER(S) IN OTHER THAN ONE- OR
 TWO-FAMILY DWELLINGS SHALL BE
 MARKED TO INDICATE EACH DEVICE OR EQUIPMENT WHERE THE
 POWER ORIGINATES.
  
  