2017-07-13 10:43:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SYSTEM SHALL BE SIZED FOR MAX GAS DEMAND PER FBC
 FG 402.2 THE TANKLESS WATER MAX LOAD SHALL BE LISTED AT
 199 MBH NOT 25 MBH WHICH WILL MAKE YOUR TOTAL GAS LOAD
 ON THE SYSTEM 319 MBH PLEASE CLARIFY ON PLAN. PER WPB
 AMEND TO FBC 107.2.1
  
 2. PER THE MANUFACTURE SPECS THE TANKLESS HEATER IS
 DESIGNED TO BE A DIRECT VENT THE DETAIL DRAWING ON SHT
 P-2.0 IS SHOWING ONLY EXAUST PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 3. THIS APPEARS TO BE DESIGNED AS A 2LB SYSTEM IF SO
 PLEASE SHOW REGULATORS AT EACH APPLIANCE. PER FBC FG
 410.1
  
 4 PLEASE PROVIDE MANUFACTURE SPECIFICATION THAT SHOW
 THE STANDARDS THAT THEY COMPLY WITH THE ONES THAT ARE
 IN THE SUBMITTAL PACKAGE NOW DO NOT SHOW COMPLIANCE.
 PER FBC FG 301.3 AND 301.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  