Plan Review Notes For Permit 17041135 |
Permit Number |
17041135 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-22 16:24:39 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | PLUMBING COMMENTS: DENIED | | | | 1. PLEASE PROVIDE DETAIL AND SIZING CALC FOR OVERFLOW | | SCUPPER ON ROOF TO SHOW COMPLIANCE WITH. FBC RES | | 903.4.1 | | | | 2. SHT. P-1.0 + P-3.0 THE SOIL STACK SHALL CONNECT TO | | BUILDING DRAIN DOWN STEAM OF TH POWDER ROOM BATHROOM | | GROUP. PER FBC RES P3108.1 | | | | 3. SHT P-2.0 DETAIL #7 SHOWS A FLOOR MOUNT TANK TYPE | | WATER HEATER THE OTHER DRAWING SHOW A TANKLESS PLEASE | | CLARIFY. WPB AMEND TO FBC 107.2.1 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|