Text |
2017-05-22 16:43:45 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| GAS COMMENTS: DENIED 5/22/17 |
| |
| 1. THE GAS WATER HEATER ON THE RISER AND GAS FIXTURE |
| LOAD SUMMERY LIST THE MBH AT 25 ON SHT P-1.0 NOTE #7 IT |
| LIST THE MBH AT 199 PLEASE CLARIFY PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 2. THE LONGEST RUN IS LISTED AT 20' THE MEASUREMENTS ON |
| THE RISER ADD UP TO 56' PLEASE CLARIFY. PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| 3. USING THE LONGEST RUN METHOD OF SIZING, YOUR FIRST |
| SECTION OF PIPE IS UNDERSIZED PER FBC FG TABLE |
| 402.4(10(20) IT SHOULD BE 11/4" THE SECTION TO TEE FOR |
| THE DRYER SHOULD BE 1" THE SECTION TO TANKLESS HEATER |
| SHOULD BE 1" |
| |
| 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| FBC-2014 FUEL GAS CODE SEC. 304. |
| |
| 5. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE |
| SEC. 502 THRU 505. |
| |
| 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND |
| INSTALLATION GUIDE FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2014 FUEL GAS SEC. 402.2 |
| |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |